Permit Information
Permit NumberFIR13-00672
StatusFinaled
Name LOCAL FIRE AND SECURITY
Site Address 10148 W EMERALD ST
Project NameWinCo Foods C2
Customer Number 
ePlanReviewNo
Description
Add smoke detection and notification in common areas. Add new NAC panel. New detectors will connect to an existing fire alarm panel. Associated building permit: BLD13-02637.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/10/20141/10/20141/10/2014PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/31/201312/31/201312/31/2013PPART
DetailsTroy Cobbley
A temporary was given with Romeo's permission. At issue are the strobes whose effect can not be seen in all areas as required in NFPA 72 sections 18.5.4.1 through 18.5.4.3
INSP-Final Inspection12/30/201312/30/201312/30/2013PCANC
DetailsTroy Cobbley
Cancel per BRIAN Phone #: ###-####