Permit Information
Permit NumberFIR14-00047
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 6401 S EISENMAN RD Unit: 105
Project NameQUARRY VIEW SUITE #105 & #106
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration.

Permit is to build out a 4,774 metal milling and office tenant (4,247 sq. ft. 1st floor / 527 sq. ft. 2nd floor)in an existing 20,268 square foot shell and core building (BLD07-00349). This building if fire sprinklered for non-separated uses and area increase. Approval contingent upon adhering to the approved plans on file. Work to include: [construction of interior non-bearing walls to create a private office, two open office areas, two unisex accessible restrooms, and a manufacturing area], installation of new load bearing walls / floor to create a new second floor, installation of new electrical, installation of new accessible bathroom fixtures, installation of mop sink, new kitchenette with sink, construction of a new interior open stairway, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/6/20143/6/20143/6/2014PPASS
DetailsForrest France
Verified additional coverage. Final walkthrough passed. Permit finaled.
INSP-Final Inspection3/4/20143/5/20143/5/2014PPART
DetailsForrest France
Final pending coverage below two overhead garage doors. Add sprinkler protection or reduce obstruction to meet NFPA 13.
INSP-Sprinkler Rough-in1/30/20141/31/20141/31/2014APART
DetailsForrest France
Okay to cover overhead work at the first floor additions per dated plan annotations.