INSP-Final Inspection | 3/13/2014 | 3/14/2014 | 3/14/2014 | A | PASS |
Craig D. Hanson
|
|
|
Fire Alarm system inspected and passed. cdh
|
INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 | P | FAIL |
Forrest France
|
|
|
C/N items include; notification appliances at some areas need relocated per plan keynote #1, noted overspaced, missing and unsecured notification devices, missing smoke detectors at several areas shown as existing on the plan. Detection and notification spacing has been disrupted due to remodel work and will need revised. Key note items 4 and 5 indicate door holds and a control module which are not provided. Plans do not match field conditions, install does not meet plans.
|