INSP-Final Inspection | 2/13/2014 | 2/13/2014 | 2/13/2014 | P | PASS |
Forrest France
|
|
|
Corrections verified. Hood suppression permit finaled.
|
INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 | A | FAIL |
Forrest France
|
|
|
Lights failed to shut down at the west hood, need to provide signage at the manual pull stations indicating hood served, missing necessary documentation including test certification, owner manual, specs and as-built plans.
|
INSP-Final Inspection | 2/10/2014 | 2/12/2014 | 2/12/2014 | A | FAIL |
Troy Cobbley
|
|
|
Contractor was not able to perform a realistic/cunctional test of the hood suppression system.
|