Permit Number | FIR14-00099 |
Status | Finaled |
Name |
TREASURE VALLEY FIRE PROTECTION
|
Site Address |
651 E PARKCENTER BLVD
|
Project Name | Dr. Cheryl Higer Gas Room |
Customer Number | |
ePlanReview | Yes |
Description |
Connect to the new fire service provided by the plumbing contractor. Connection shall be down stream of BFP device and up stream of any shut off valves... This shall provide 24/7 uninterupted fire service to the gas room... 1 QR dry HSW shal be provided.
Resubmittal instructions:
A. When resubmitting, reference to the FIR number at the top of this review.
B. Provide a written response to each of the following listed items.
C. All revisions must be made by full size submittal drawings, not by addendum sheets.
D. All changes must be clouded and referenced by a revision number.
E. Please, make the following changes. In addition, there are revision notes on the drawings and small document
|