INSP-Final Inspection | 8/26/2015 | 8/27/2015 | 8/27/2015 | A | PASS |
Thomas Walsh
|
|
|
Final inspection and signoff for this permit.
|
INSP-Sprinkler Rough-in/Hydro | 6/23/2015 | 6/23/2015 | 6/23/2015 | P | PASS |
Thomas Walsh
|
|
|
FS U/G supply OK to final, per Scott Arellano's email, dated 6/23/15. Hydrotest and flush of U/G supply witnessed by this office, but not documented in permit file.
|
INSP-Final Inspection | 6/11/2015 | 6/11/2015 | 6/11/2015 | P | PEND |
Thomas Walsh
|
|
|
Inspection request to final FS U/G installation, although the hydrotest and flushing could not be confirmed by reviewing completed inspections recorded in permit activities file. I called Forest to confirm that these inspections were witnessed by him, which is contended by the fire sprinkler contractor. Will advise the contractor and GC accordingly.
|
INSP-Supply line flush | 9/26/2014 | 9/29/2014 | 9/29/2014 | A | NR |
Forrest France
|
|
|
Nate is the contact. Thanks Phone #: ###-#### Inspection requested via web by Stan Beus
|
INSP-Supply line flush | 9/25/2014 | 9/26/2014 | 9/26/2014 | A | NR |
Forrest France
|
|
|
Pending water supply to complete flushing.
|
INSP-Supply line flush | 9/24/2014 | 9/25/2014 | 9/26/2014 | A | CANC |
Craig D. Hanson
|
|
|
|
INSP-Sprinkler Rough-in | 7/25/2014 | 7/28/2014 | 7/28/2014 | A | PART |
Craig D. Hanson
|
|
|
Underground, west side of building, OK to cover
|
INSP-Sprinkler Rough-in | 5/12/2014 | 5/12/2014 | 5/12/2014 | A | PART |
Forrest France
|
|
|
UG cover okayed
|
INSP-Sprinkler Rough-in | 4/9/2014 | 4/9/2014 | 4/9/2014 | P | PART |
Forrest France
|
|
|
UG fire supply line including the ductile riser and stub out to a point 10' beyond the riser okayed for bury.
|
INSP-Sprinkler Rough-in | 4/8/2014 | 4/9/2014 | 4/9/2014 | A | PART |
Forrest France
|
|
|
Verified ductile riser, thrust block and approved plan set- remainder of supply line could not be inspected due to bury already complete- need to uncover piping to finish inspection.
|
INSP-Sprinkler Rough-in | 4/7/2014 | 4/8/2014 | 4/8/2014 | P | DEFR |
Forrest France
|
|
|
This is an ug to cover. Bryan is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|