Permit NumberFIR14-00277
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 1725 E WARM SPRINGS AVE
Project NameAdams Elementary
Customer NumberUDG ONLY
ePlanReviewYes
Description
Underground only. Phoenix Fire Protection to install fire service line from stub in from United Water. FPC to be remote. Both fire service line and FDC line to be run in single common trench.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/23/20153/24/20153/25/2015PPASS
DetailsForrest France
UG fire supply line permit final approved.
INSP-Sprinkler Rough-in/Hydro8/14/20148/15/20148/15/2014APART
DetailsForrest France
UG hydrostatic testing for both the remote FDC and the UG fire supply line completed satisfactory.
INSP-Supply line flush8/13/20148/13/20148/13/2014PPART
DetailsForrest France
UG fire supply line and remote FDC flush completed.
INSP-Sprinkler Rough-in6/30/20146/30/20147/1/2014PPART
DetailsForrest France
Remote FDC piping okayed for cover.
INSP-Sprinkler Rough-in6/30/20147/1/20147/1/2014APART
DetailsForrest France
Okay to cover remainder of UG fire supply line including remote FDC piping. Need to provide seismic clearance method at the ductile riser, wrap galvanized FDC stub.
INSP-Sprinkler Rough-in6/30/20146/30/20146/30/2014ANR
DetailsForrest France
Thrust blocking not yet finished per contractor.
INSP-Sprinkler Rough-in6/25/20146/26/20146/26/2014APART
DetailsForrest France
UG fire supply line including the ductile stub and pipe to a point even with the SE corner of the building okayed for cover.