Permit Information
Permit NumberFIR14-00365
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1000 W MYRTLE ST
Project NameJUMP Area A Helix
Customer Number 
ePlanReviewYes
Description
Connect to existing fire pump at level 1 helix and extend new wet and dry systems to protect the remaing areas of the JUMP building for light and ordinary hazards levels 1 through 6. Extended coverage and standard spray sprinklers have been utilized
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/24/201511/25/201511/25/2015APASS
DetailsJim Page
Fire sprinkler inspections completed.
INSP-Sprinkler Rough-in/Hydro8/18/20158/18/20158/18/2015PPASS
DetailsThomas Walsh
Hydrostatic test of FDC supply line for the 11th street supply line (200 psi @ 2hours) -PASSED.NOTE: Permit for FSUG is FIR13-00167
INSP-Final Inspection8/10/20158/10/20158/10/2015PPART
DetailsThomas Walsh
Reinspection of fire sprinkler systems for Helix and above ground FP systems, including inspection of punchlist items from last inspection. All punchlist items adeqautely addressed.
Main WF electric bell to be installed outside of main FACP control room.
Also tested main PIVs (9th and 11th streets). Both were not working correctly and will be retested after repaired/replaced.
INSP-Final Inspection8/6/20158/7/20158/7/2015APART
DetailsThomas Walsh
Final inspection for Helix structure and above ground parking garage, and all rooms located above the parking garage.
NOTE: Some DP heads in the parking garage not installed yet. Some other minor punchlist items remain that will require re-inspection. Also, exterior alarm bell required to be installed near exterior of the command center, and be tied into all waterflow alarms to indicate a water flow from any system within the structure.
INSP-Sprinkler Rough-in/Hydro7/31/20158/3/20158/3/2015PPASS
DetailsThomas Walsh
Fire pump commissioning test with MFG's rep. Tested 0 flow. 100% and 150% with generator and both supplies open. All tested OK. Pump test report to e emailed to Tim Frost.
INSP-Conference7/21/20157/21/20157/21/2015PDONE
DetailsThomas Walsh
Meeting with elect. contractor (Tony) to discuss clearance around hose valve from emergency lighting unit.
INSP-Alarm Testing7/12/20157/12/20157/12/2015PPART
DetailsThomas Walsh
Test of dry pipe valves for 2nd and 3rd floor Helix structure, which includes ramp and some areas surrounding the ramp. Trip test of DP valves, including trip tests, low-air, waterflow and tampers. All tested OK
NOTE: Other systems protecting the Helix (floors 1 thru 6) have now been tested and passed. Kitchen and 2nd floor lobby on another permit.
INSP-Final Inspection7/10/20157/10/20157/10/2015PPASS
DetailsThomas Walsh
Trip test of the dry-pipe valves for the Helix at levels 2 and 3. All tested OK
INSP-Final Inspection7/8/20157/9/20157/9/2015PPART
DetailsThomas Walsh
Inspection of Helix dry-pipe systems for fire alarm interface, including water flows, tampers, low-air signals and including trip tests - all floors except levels 2 and 3.
All tested OK and within 60 seconds of flow test.
NOTE: 6th floor wet system not programed into alarm system - will retest.
INSP-Sprinkler Rough-in/Hydro6/19/20156/19/20156/19/2015PPASS
DetailsThomas Walsh
24 hour air test of dry pipe valves for six (6) systems, including 2nd floor Helix, 3rd floor Helix, 3rd floor parking garage, 4th floor Helix, 4th floor parking garage, and 5th floor Helix - all system air tests held pressure.
PASSED
INSP-Sprinkler Rough-in/Hydro6/18/20156/18/20156/18/2015PPART
DetailsThomas Walsh
This is a 24 hour air test of six (6) dry pipe valves, as floows;
2nd floor helix, 3rd floor helix, 3rd floor P/G, 4th floor helix, 4th floor P/G and 5th floor helix. Will retest air pressures at 1:30pm on 6/19.
INSP-Sprinkler Rough-in/Hydro6/10/20156/10/20156/10/2015PCANC
DetailsThomas Walsh
Wrong permit # called in for this inspection. Will add inspection to the correct permit # FIR13-00275
INSP-Sprinkler Rough-in/Hydro5/16/20155/16/20155/16/2015PPASS
DetailsThomas Walsh
Hydrotest of helix dry systems - levels 2, 4 and 5, and 5th floor wet-pipe system
INSP-Sprinkler Rough-in9/19/20149/22/20149/22/2014APART
DetailsForrest France
Inspection for cover at the 2nd and 3rd floor service elevator lobby drop ceilings and 2nd level 3" dry main at west side heilix. Discussed project schedule and work completed to date.