INSP-Final Inspection | 10/2/2014 | 10/3/2014 | 10/3/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/1/2014 | 10/2/2014 | 10/2/2014 | A | FAIL |
Troy Cobbley
|
|
|
As-builts showing the correct zones need to be submitted, low air switch did not work, smoke detector needs to be mounted per code, manual pull stations are mounted too high, panel needs to be set up to report battery troubles from a single battery.
|