Permit Information
Permit NumberFIR14-00417
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 10826 W FLORENCE DR
Project NameCORDILLERA 4 PLEX BLDG 2
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting, (4) two level apartments (townhouses). CPVC piping and extended coverage sprinklers are being utilized. The underground is 2” poly pipe. There will be a 1½” FDC.

(CORDILLERA DEVELOPMENT - BLDG 2) To construct a new 3,668 sq. ft., two story, Four unit, apartment building. Units 'A' have one bedroom, one den, and two bathrooms. Units 'B' have two bedrooms, and two bathrooms. All 4 dwelling units have their own independent exit. All construction per the approved plans, attached plan review report, and all other reviewing agencies approvals. One hour fire-partition separations are required between dwelling units. This building is required to be fire sprinklered. The fire sprinkler system shall be per NFPA 13R as regulated by the fire department. DRH13-00288 Per Planning and Zoning. See BLD14-00203 for Building Plan Review Report. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/27/201410/28/201410/28/2014PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro10/24/201410/24/201410/24/2014PPASS
DetailsTroy Cobbley
Ovehead hydro test passed.
INSP-Sprinkler Rough-in/Hydro10/23/201410/23/201410/23/2014PFAIL
DetailsTroy Cobbley
Overhead hydro test failed
INSP-Supply line flush10/22/201410/22/201410/22/2014PPASS
DetailsCraig D. Hanson
Flush good. Concrete around riser needs to be broken up and looked at on another inspection.
INSP-Supply line flush9/30/201410/1/201410/1/2014PCANC
DetailsTroy Cobbley
Not ready
INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014PCANC
DetailsTroy Cobbley
Brandon-underground flushing Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro9/16/20149/17/20149/17/2014PCANC
DetailsTroy Cobbley
Underground hydro - Brandon Phone #: ###-####
INSP-Sprinkler Rough-in9/16/20149/17/20149/17/2014APASS
DetailsTroy Cobbley
Rough-in passed .Tenting passed. Piping is ok to cover.
INSP-Sprinkler Rough-in9/11/20149/12/20149/12/2014APASS
DetailsTroy Cobbley
Rough-in passed. Piping can not be covered until a tenting inspection has been performed
INSP-Sprinkler Rough-in8/20/20148/20/20148/20/2014PPASS
DetailsTroy Cobbley
Underground supply is ok to cover