Permit NumberFIR14-00443
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 6724 W IRVING ST
Project NameAberdeen 4-Plex: #6724 Irving
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a 4-unit apartment building. CPVC pipe and extended throw residential sprinklers are being utilized.

L13B2 - 6724 Irving - (Bldg 5) To construct a new 3,800 sq. ft., two story, Four unit, apartment building. Each unit has two bedrooms, and two bathrooms. The 1st story units are required to be Type 'B' units. All units share a common path of egress into and through a 1-hour rated exit corridor with 20 minute fire-resistive, listed, labeled, self-closing door assemblies from the dwelling units into the corridor. All construction per the approved plans, attached plan review report, and all other reviewing agencies approvals. One hour fire-partitions and one hour horizontal assemblies are required between dwelling units. This building is required to be fire sprinklered. The fire sprinkler system shall be per NFPA 13R as regulated by the fire department. DRH13-00276 & CUP13-00017 Per Planning and Zoning. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/26/20149/29/20149/29/2014PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro8/25/20148/26/20148/26/2014PPASS
DetailsTroy Cobbley
Rough-in and overhead hydro test passed. Piping can be covered.
INSP-Sprinkler Rough-in/Hydro8/1/20148/1/20148/1/2014PPASS
DetailsTroy Cobbley
Hydro test of the FDC supply piping passed
INSP-Sprinkler Rough-in/Hydro7/31/20148/1/20148/1/2014AFAIL
DetailsTroy Cobbley
Visable drop in guage pressure of 5psi
INSP-Sprinkler Rough-in/Hydro7/28/20147/31/20147/31/2014APART
DetailsTroy Cobbley
First and second floor hydro tests passed. The FDC supply hydro test failed due to visible leakage at the ball drip. The sprinkler rough-in passed but piping can not be covered since no tenting has been installed/inspected at this point in time.
INSP-Supply line flush7/28/20147/31/20147/31/2014ACANC
DetailsTroy Cobbley
Mike M is the contact. Thanks Phone #: ###-#### Inspection requested via web by Stan Beus