INSP-Final Inspection | 3/24/2015 | 3/25/2015 | 3/25/2015 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 3/24/2015 | 3/26/2015 | 3/24/2015 | A | CANC |
Troy Cobbley
|
|
|
Mike S is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Final Inspection | 3/20/2015 | 3/24/2015 | 3/24/2015 | A | FAIL |
Troy Cobbley
|
|
|
No outside electric alarm bell has been installed. Flow switch comes in at the FACP as a supervisory signal. No signage on riser room door.
|
INSP-Supply line flush | 3/16/2015 | 3/18/2015 | 3/18/2015 | A | PASS |
Troy Cobbley
|
|
|
Underground flush and forward flush test passed inspection
|
INSP-Supply line flush | 2/25/2015 | 3/2/2015 | 3/2/2015 | A | CANC |
Troy Cobbley
|
|
|
No underground flush performed due to United Water not having the water turned on.
|
INSP-Sprinkler Rough-in | 2/27/2015 | 3/2/2015 | 3/2/2015 | P | CANC |
Troy Cobbley
|
|
|
United Water has not turned on the water supply yet. No forward flush performed.
|
INSP-Sprinkler Rough-in/Hydro | 2/25/2015 | 2/26/2015 | 2/26/2015 | A | PASS |
Troy Cobbley
|
|
|
Overhead hydro test passed. Hanger added
|
INSP-Sprinkler Rough-in/Hydro | 2/25/2015 | 2/26/2015 | 2/25/2015 | A | CANC |
Troy Cobbley
|
|
|
RTC/Hydro. Mike S is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 2/25/2015 | 2/26/2015 | 2/25/2015 | P | CANC |
Troy Cobbley
|
|
|
Mike Phone #: ###-#### Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in/Hydro | 2/24/2015 | 2/25/2015 | 2/25/2015 | A | PART |
Troy Cobbley
|
|
|
OH/Hydro inspection failed. Rough to cover on remaining ceilings passed. I noted one pendant needs an additional hanger.
|
INSP-Conference | 11/25/2014 | 11/25/2014 | 11/26/2014 | P | DONE |
Troy Cobbley
|
|
|
Mike and I discussed the location of the FDC and the control valve for the Server Room. I deferred any changes to Tim Frost for approval.
|