Permit NumberFIR14-00603
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1570 S LUSK PL
Project NameLusk Place Apartments
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protect a parking garage with two dry systems. All other work, including but not limited to the standpipe and wall hydrants are excluded from this review. It is anticipated these items will be reviewed when the upper levels are submitted. Dry system # 1is approximately 37856 ft^2 and is designed as a loop. Dry system #2 is approximately 25300 ft^2 and is designed as a tree. 6” underground piping supplies a 6” backflow preventer and 6” header. The header has the two 4” dry systems and a 6” combination standpipe.

The underground is under permit FIR14-00477

Lusk Apartments - (Structural Foundation including First Floor Podium) - To construct the foundation and first level concrete podium for a new approximate 253,650 sq. ft., four story building and related site improvements. This permit will also include site grading, drainage and underground utilities. The building will be constructed of concrete foundation with wood framed structure above. Work under this permit shall not proceed beyond the foundation and first floor podium until final approval of the plans and issuance of the next phase building permit. That permit has not yet been applied for. As owner or designated agent, I acknowledge that I am performing this work at my own risk without assurance that the permit for the entire building structure will be granted, and I agree to make any modifications to the foundation and building structure work as may be required to comply with the City Codes and the final approved building plans and conditions. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/2/20159/3/20159/3/2015APASS
DetailsThomas Walsh
Final inspection of fire sprinklers for the parking garage area of the building - PASSED. Contractor cert. of completion signed off and will be emailed to the PDS office.
INSP-Final Inspection8/6/20158/7/20158/7/2015APART
DetailsThomas Walsh
Final inspection for garage dry pipe systems. Final passed, except for record of completion (ROC) paperwork not completed yet.
INSP-Final Inspection8/6/20158/6/20158/6/2015PFAIL
DetailsThomas Walsh
Final inspection requested for parking garage permit, however noted dissimilar sprinklers (temp ratings) for several sprinklers located in the stair enclosures. Contractor agreed to inspect all and change out as needed to reflect proper temp. ratings per plans.
INSP-Sprinkler Rough-in8/4/20158/5/20158/5/2015APASS
DetailsThomas Walsh
Retest of dry pipe system #1 for the north side parking garage.
PASSED - tripped within 58 seconds to waterflow.
INSP-Sprinkler Rough-in8/3/20158/4/20158/4/2015AFAIL
DetailsThomas Walsh
Trip test of dry pipe systems protecting the parng garage. The south system tested OK, wheras the north system did not meet 60 seconds trip test. Suspected some blockage within system. Will retest after the problem is addressed.
INSP-Sprinkler Rough-in8/3/20158/3/20158/4/2015PCANC
DetailsThomas Walsh
Due to time constraints, this inspection could ntot be completed. Will reschedule for 8/4.
INSP-Alarm Testing7/30/20157/31/20157/31/2015AFAIL
DetailsThomas Walsh
Test of all dry pipe system protecting the parking garage (x2), the attic (x2) and the clubhouse. The systems protecting the attic space on the south side, and the clubhouse tested OK. The other three (3) systems failed the 60 second trip test, and will require accelerators. All tampers tested OK. Low air for the dry systems also not tested this visit.
INSP-Alarm Testing7/29/20157/30/20157/30/2015APART
DetailsThomas Walsh
Partial fire alarm interface testing, including all wet pipe systems, except for the clubhouse, including water flows, tampers, etc.
INSP-Sprinkler Rough-in7/23/20157/23/20157/24/2015PPASS
DetailsJim Page
24 hour air test passed/complete on both dry systems in parking structure.
INSP-Sprinkler Rough-in/Hydro7/22/20157/22/20157/22/2015PPASS
DetailsJim Page
Hydrostatic test passed/complete on both dry systems covering parking garage, 1st level,
INSP-Sprinkler Rough-in/Hydro7/21/20157/22/20157/22/2015ACANC
DetailsJim Page
This is a hydro request for the dry system. Mark is the contact. Thanks. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in/Hydro5/29/20155/29/20155/29/2015PPART
DetailsThomas Walsh
Rough to cover inspection for two (2) dry pipe systems protecting two halves of the parking garage. PASSED - OK to cover.