INSP-Final Inspection | 10/23/2014 | 10/24/2014 | 10/24/2014 | A | PASS |
Forrest France
|
|
|
Verified noted correction items, fire alarm work passed final inspection.
|
INSP-Final Inspection | 10/23/2014 | 10/23/2014 | 10/23/2014 | P | FAIL |
Forrest France
|
|
|
Completed initial walkthrough and testing of occupant notification. Items noted include; non-functional speaker at the audit room, audibility not met at the SW conference room, need to verify operations under fire alarm condition at both delayed egress doors when powered, need to verify two DH and WON door operability without bypass enabled.
|