Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR14-00667
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8000 W FRANKLIN RD
Project NameCHICK-FIL-A
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of a new restaurant with above and below protection. The system is designed as a tree with 3” riser and backflow preventer.

The underground piping was installed under permit FIR14-00521

New Chick-fil-A Drive-thru Restaurant - To demolish and remove an existing 5,530 sq. ft. restaurant building and construct a new 4,600 square foot, one story, wood framed, fast food restaurant with drive-thru window. This permit also includes all related site improvements. This building will be fully fire sprinklered. The sprinklers are required because the occupant load of the building fire area exceeds 100.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/18/201411/19/201411/19/2014APASS
DetailsTroy Cobbley
Dry system trip passed. Permit finaled
INSP-Final Inspection11/12/201411/13/201411/14/2014PPART
DetailsForrest France
Fire sprinkler permit work passed final walkthrough- escutcheon replaced, tape and paper removed at service entrance head, outside waterflow bell repaired while on site. Sprinkler monitoring verified. Final pending full trip test of the new dry system valve- not completed due to weather conditions at the time.
INSP-Sprinkler Rough-in/Hydro10/29/201410/29/201410/29/2014PPASS
DetailsTroy Cobbley
Overhead wet and dry systems passed hydro test.
INSP-Sprinkler Rough-in10/23/201410/24/201410/27/2014APASS
DetailsTroy Cobbley
Rough-in passed. Piping can be covered as marked on the approved plans. This includes doghouses.
INSP-Sprinkler Rough-in10/23/201410/24/201410/24/2014APASS
DetailsTroy Cobbley
24 hour air test passed
INSP-Sprinkler Rough-in/Hydro10/23/201410/24/201410/24/2014APASS
DetailsTroy Cobbley
24 hour air test on dry system passed
INSP-Sprinkler Rough-in10/22/201410/23/201410/23/2014APASS
DetailsTroy Cobbley
started 24 hr air test with marked guage at 8:00am
INSP-Sprinkler Rough-in10/21/201410/21/201410/21/2014PPART
DetailsForrest France
OH fire sprinkler work at the grid ceilings in the kitchen, multi-purpose, and office rooms as marked and dated on approved plans okayed for cover.
INSP-Supply line flush10/20/201410/21/201410/21/2014APART
DetailsForrest France
UG fire supply line flush completed. Inspection request intended for UG permit FIR14-00521.
INSP-Sprinkler Rough-in9/23/20149/24/20149/24/2014PPASS
DetailsTroy Cobbley
See the city approved plans for locations where the sprinkler piping can be covered by the new hardlids.