INSP-Final Inspection | 9/23/2015 | 9/23/2015 | 9/23/2015 | P | PASS |
Thomas Walsh
|
|
|
Final inspection of wet and dry pipe fire sprinkler systems - PASSED.
|
INSP-Sprinkler Rough-in/Hydro | 9/22/2015 | 9/22/2015 | 9/22/2015 | P | PART |
Thomas Walsh
|
|
|
Completion of 24 hour air test for dry- pipe system (Bldg. J) - PASSED
|
INSP-Final Inspection | 9/17/2015 | 9/21/2015 | 9/21/2015 | P | PART |
Thomas Walsh
|
|
|
Final inspection of wet pipe and dry pipe susyems - Not Ready - DP valve currently under 24 hour air test, and a couple of heads need to be replaced (painted) and a few escutcheon rings need to be installed. All FA interface tested OK
|
INSP-Sprinkler Rough-in | 9/17/2015 | 9/21/2015 | 9/21/2015 | P | PART |
Thomas Walsh
|
|
|
Duplicate request - Fire sprinkler system test with fire alarm interface, including water flows, tampers, trip test of dry pipe valve, exterior bell, etc. All tested OK - trip test of DP valve exceeded 60 seconds for water to IT - Contractor stated that system met <500 gpm to not have to provide water to IT within 60 seconds. Contractor agreed to provide supporting documentation that system meets this criteria. DP system put on 24 hour air test at 2:00pm - will retest tomorrow at same time.
|
INSP-Sprinkler Rough-in/Hydro | 9/17/2015 | 9/21/2015 | 9/21/2015 | P | PART |
Thomas Walsh
|
|
|
Fire sprinkler system test with fire alarm interface, including water flows, tampers, trip test of dry pipe valve, exterior bell, etc. All tested OK - trip test of DP valve exceeded 60 seconds for water to IT - Contractor stated that system met <500 gpm to not have to provide water to IT within 60 seconds. Contractor agreed to provide supporting documentation that system meets this criteria. DP system put on 24 hour air test at 2:00pm - will retest tomorrow at same time.
|
INSP-Sprinkler Rough-in | 7/24/2015 | 7/27/2015 | 7/27/2015 | A | CANC |
Jim Page
|
|
|
Incorrect FIR number for todays inpsection, FIR number for building K to be called in by contractor, verified per conversation with onsite point of contact, Leroy, phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 5/18/2015 | 5/19/2015 | 5/19/2015 | A | PASS |
Thomas Walsh
|
|
|
Hydrotest of wet and dry pipe systems - no leaks noted. Pressure held for 2 hours.
|
INSP-Sprinkler Rough-in/Hydro | 5/18/2015 | 5/19/2015 | 5/18/2015 | P | CANC |
Troy Cobbley
|
|
|
Rough-in Hydro Wet and Dry Please call Leroy 30 min prior ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|
INSP-Sprinkler Rough-in | 5/14/2015 | 5/14/2015 | 5/16/2015 | P | PASS |
Thomas Walsh
|
|
|
Rough in inspection of Bldg. J (skilled nursing facility) wet-pipe system.
|
INSP-Sprinkler Rough-in/Hydro | 5/15/2015 | 5/15/2015 | 5/15/2015 | P | PASS |
Thomas Walsh
|
|
|
Rough-in inspection of Bldg J - skilled nursing facility. Found 2 drips in weld connections, that will be repaired prior to hydro.; Phone #: ###-####
|
INSP-Sprinkler Rough-in | 2/4/2015 | 2/4/2015 | 2/4/2015 | A | PART |
Forrest France
|
|
|
Verification of previous C/N items for completion.
|
INSP-Sprinkler Rough-in | 2/3/2015 | 2/3/2015 | 2/3/2015 | A | PART |
Forrest France
|
|
|
Completed rough-in for the dry system building J. Items noted include; replace one CC2 sprinkler with the correct type indicated per plan, remove temp vapor barrier obstructing upright coverage above entry vestibule, two ssu exceed min separation at removed draft stop, missing coverage at one overbuild, provide verification plumbing chases meet non-combustible criteria or install sprinkler protection- ref. to plan annotations.
|
INSP-Sprinkler Rough-in | 2/2/2015 | 2/2/2015 | 2/2/2015 | P | PART |
Forrest France
|
|
|
Rough-in at portions of the dry and wet systems only.
|
INSP-Sprinkler Rough-in | 1/16/2015 | 1/20/2015 | 1/20/2015 | A | NR |
Forrest France
|
|
|
Bldg J dry and partial wet Pls call Leroy 30 mins prior Phone #: ###-#### Inspection requested via web by Jacci Hunt *NR per contractor
|
INSP-Sprinkler Rough-in | 1/15/2015 | 1/16/2015 | 1/16/2015 | P | CANC |
Forrest France
|
|
|
BLdg J dry and partial wet Please call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|