Permit NumberFIR14-00724
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 5301 E WARM SPRINGS AVE
Project NameThe Terraces of Boise Garage2
Customer Number 
ePlanReviewYes
Description
TOB, FA submittal on Garage#2 consists on complete notification system, sprinkler monitoring and elevators interface. New Transponder panel to be networked within the complex. Associated with building permit BLD13-00180.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  1/8/2019 DONE
DetailsLee G Meredith
INSP-Final Inspection10/29/201510/29/201510/29/2015PPASS
DetailsThomas Walsh
Fire alarm system testing for Garage #2 passed test/inspection.
INSP-Final Inspection10/21/201510/26/201510/26/2015APART
DetailsThomas Walsh
Fire alarm system test of wings F & G, including all unit SDs. corridor SDs, manual pulls, notification devices (audibility), FSDs, elevator recall functions, etc. All tested OK. Two unit SDs had to be reprogrammed to activate correctly.
NOTE: All fire sprinkler system testing completed with wing E test.
INSP-Alarm Testing10/6/201510/6/201510/6/2015PPART
DetailsThomas Walsh
Trip test of dry pipe valve for wings EF&G attics, including low-air alarm, tamper and pressure switch - all tested OK.
NOTE: Elevatorfor wing E was not tested - recall functions not operating due to some fault in the elevator system. Will retest after elevator is functioning properly.
Note2: There are a couple of FA devices at the separation between Wing E & F, that need to be functional for TCO of wing E. Contractor agreed to rewire these devices to make them operational for Wing E TCO.
INSP-Final Inspection10/1/201510/5/201510/5/2015APART
DetailsThomas Walsh
Test of fire alarm system for wing E - all floors including a portion of the parking garage system, includingt test of all in-room smoke detectors, corridor SDs, manual pulls, SFDs, waterflows and tampers. All tested OK, except for the dry-pipe attic sprinkler system which will have to be retested after an accelerator device is added to this system.
NOTE: Wings F & G not ready for testing yet, although there are a few devices in bldg. F that will have to be made functional as they are located in the wing E TCO area. Also, elevator testing for this wing not performed yet - the state is scheduled to conduct their test tomorrow.