Permit Information
Permit NumberFIR14-00902
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 10238 W ALPINE MEADOW ST
Project NameBarga Residence
Customer Number 
ePlanReviewYes
Description
[Barga Residences] - Shilo will install a new fire sprinkle system into the new Barga Residence per NFPA 13, 2013.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/5/20155/6/20155/6/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/4/20155/4/20155/4/2015PFAIL
DetailsTroy Cobbley
Flow switch kept sticking and appears to need replacing.
INSP-Final Inspection4/21/20154/28/20154/28/2015AFAIL
DetailsTroy Cobbley
The backflow preventor installed does not match the city approved plans. Also the outside electric alarm bell has not been installed. Inspetion stopped.
INSP-Sprinkler Rough-in1/22/20151/22/20151/22/2015PPASS
DetailsTroy Cobbley
Tenting passed. Piping can be covered.
INSP-Supply line flush1/13/20151/13/20151/13/2015PPASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in1/13/20151/13/20151/13/2015PFAIL
DetailsTroy Cobbley
This was a tenting inspection. I have concerns in four locations where it appears that extra long pendant drops will not have protection from cold air. Two are located at the master bath and two locatated at the bedrooms at the opposite end of the house.
INSP-Sprinkler Rough-in/Hydro12/31/20141/5/20151/5/2015PPASS
DetailsTroy Cobbley
Rough-in passed. I spoke to Cam about a possible pendant head addition in the walk-in shower and I spoke to Tyler about the need for proper clearance at the cpvc riser. Piping can not be covered until a tenting inspection has been passed.