Permit Information
Permit NumberFIR15-00039
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1666 W RIDENBAUGH ST
Project NameADA COUNTY PARAMEDICS
Customer Number 
ePlanReviewYes
Description
[ADA County Paramedics]
The fire sprinkler scope of work consists of single floor building. Half of the facility is residential area and the other half is the vehicle bay. There is a 4” riser, with backflow preventer, 3” cross mains and 1”, 1 /4” branch lines.
(ADA County Paramedics) (Station 17) Permit to renovation an existing 2,136 sq ft existing paramedic station and add 88 sq ft to the day room for a total of 2,224. Scope of work to includes exterior change to the site as shown in the civil drawings. There will be interior demolition as shown on the new plans. New foundation, exterior wall and roof will be installed in addition with the new roof structure extending over entire building. New interior lay out per approved plans. All interior finish material shall meet the requirements of IBC chapter 8. Plumbing, mechanical and electrical modifications shall be per the engineered plans. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **ajs**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/6/20177/7/20177/6/2017APASS
DetailsJim Page
Final inspection for fire sprinklers completed on 6/22/2015.
INSP-Final Inspection6/22/20156/22/20156/22/2015PPASS
DetailsKatie Marron
Additional head installed to cover obstructed area. Scope of work complete. Permit finaled.
INSP-Final Inspection6/19/20156/19/20156/19/2015PPART
DetailsKatie Marron
Final pending corrections to obstructed head in vehicle bay.
INSP-Supply line flush6/2/20156/3/20156/3/2015APASS
DetailsKatie Marron
Underground flush of new 4" main completed satisfactory.
INSP-Sprinkler Rough-in/Hydro5/27/20155/27/20155/27/2015PPASS
DetailsJim Page
Underground hydrostatic test complete/passed.
INSP-Sprinkler Rough-in/Hydro3/18/20153/18/20153/18/2015PPART
DetailsForrest France
Overhead rough-in inspection completed. Need to verify insulation fill above the vehicle bay at the non-sprinklered combustible concealed spaces to meet allowable exceptions per NFPA 13, need to relocate one overspaced upright above the report room. OH hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro3/16/20153/17/20153/17/2015PCANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in3/12/20153/12/20153/12/2015APASS
DetailsTroy Cobbley
Underground ok to cover. All land scaping to be level with the sidewalk or the minimum 4'6" won"t be met
INSP-Sprinkler Rough-in3/11/20153/11/20153/12/2015PCANC
DetailsTroy Cobbley
Overbooked. Rescheduled for 3/12/2015
INSP-Sprinkler Rough-in2/23/20152/23/20152/23/2015PPART
DetailsForrest France
The 4" IBR only, inspected for cover at this time. *NOTE- thrust blocking is not provided- contractor has choosen to utilize rodding method.