INSP-Final Inspection | 8/14/2015 | 8/19/2015 | 8/19/2015 | P | PASS |
Jim Page
|
|
|
Fire alarm inspection passed/complete
|
INSP-Final Inspection | 7/2/2015 | 7/9/2015 | 7/9/2015 | A | FAIL |
Troy Cobbley
|
|
|
No actual testing of devices was performed due to changes needed. As-builts will be needed showing the revised wall layout, candella changes on strobes, additional strobe in Kitchen and additional manual pull stations at the exit doors. Stamped approved plans were not on site yet for the fire alarm system. Two strobes had been mounted too low and were adjusted while I was on site.
|