Permit NumberFIR15-00255
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4971 W OVERLAND RD
Project NamePrimary Health Orchard
Customer Number 
ePlanReviewYes
Description
[Primary Health Orchard]
The fire sprinkler scope of work consists of new 4”x75’± C-900 piping with necessary fittings and thrust blocks. The 4” underground supplies a 3” backflow preventer and 3” riser. The 3” main supplies a 2½” cross main with 1¼” branch lines. The system has upright protection above the ceiling and pendent sprinklers below the ceiling. The piping is steel with standard coverage quick response sprinklers.

(PRIMARY HEALTH 4969)Permit to demolish existing Raedean's Restaurant and related site improvements, and construct new 5,618 sf ft PRIMARY HEALTH Medical Clinic as shown on approved plans and documents with limited site improvements and landscaping. This building is constructed as Type VB. All construction shall be per the approved plans and attached comment list. This building is fully Fire Sprinklered with an approved Fire Alarm system. **ajs**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/30/201510/1/201510/1/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/29/20159/30/20159/30/2015PFAIL
DetailsTroy Cobbley
Need to forward flush test the backflow, need cap on the FDC connection, need back flow certification and need the pressure relief vavle.
INSP-Sprinkler Rough-in/Hydro8/19/20158/20/20158/20/2015ACANC
DetailsTroy Cobbley
Underground hydo test already passed
INSP-Sprinkler Rough-in/Hydro8/18/20158/19/20158/19/2015PPASS
DetailsJim Page
Overhead hydrostatic test passed/complete, do not see any comments for underground hydrostatic test, underground still needs hydrostatic test.
INSP-Sprinkler Rough-in8/18/20158/19/20158/19/2015PPASS
DetailsJim Page
Rough to cover inspection passed/complete, entire project approved for cover.
INSP-Sprinkler Rough-in7/30/20157/31/20157/31/2015APASS
DetailsTroy Cobbley
The rough in inspection for 4 dry heads in the chases passed. Piping can be covered.
INSP-Sprinkler Rough-in7/8/20157/9/20157/9/2015APASS
DetailsTroy Cobbley
Lobby sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in7/8/20157/8/20157/8/2015PPASS
DetailsTroy Cobbley
See the city approved plans for locations (hard lids) where the piping is marked "ok" for cover. Main Lobby is ok to cover as well.
INSP-Supply line flush7/6/20157/6/20157/6/2015PPASS
DetailsTroy Cobbley
Underground flush passed
INSP-Supply line flush6/30/20157/1/20157/1/2015AFAIL
DetailsTroy Cobbley
I left message on voice mail I was on the way. Got to job site and could not make contact with contractor. No flush performed.
INSP-Supply line flush6/29/20156/30/20156/30/2015PPART
DetailsTroy Cobbley
No underground flush performed. Underground hydro passed
INSP-Sprinkler Rough-in5/18/20155/18/20155/18/2015PPASS
DetailsTroy Cobbley
Underground piping okay for cover