Permit Information
Permit NumberFIR15-00303
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7996 W OVERLAND RD
Project NameDiscount Tire
Customer Number 
ePlanReviewYes
Description
[Discount Tire]
The fire sprinkler scope of work consists of protecting a single level building with a grid type system. The majority of the building is protected with ESFR type sprinklers. The rack storage is 18’ high with a level of grating at 9’. The sales area and “dead tire storage” are protected as OH II. There is an 8” riser with backflow preventer. The riser is in a one hour rated room.

Rubber tire storage up to 18’ on-side or on tread no pallets or horizontal barriers.

The underground was install under permit FIR15-00297

"Discount Tire Store" For the construction of a new 7,373 sq. ft. one story Discount Tire Store with a 2,180 sq. ft. mezzanine including grading and drainage and general site work and utilities. The building is constructed of CMU exterior walls, noncombustible interior framing and a steel roof truss system. (type IIB). This building is fully fire sprinklered for tire storage and a mezzanine greater than 1/3 of the area served by the mezzanine. This building also is required to have a voice/alarm per section 505.2.1 exception 2 (2012 IBC) CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/23/201511/23/201511/23/2015PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection11/2/201511/2/201511/2/2015PFAIL
DetailsTroy Cobbley
All items completed except for forward flush and fire alarm interconnections.
INSP-Sprinkler Rough-in/Hydro10/29/201510/29/201510/29/2015PPASS
DetailsTroy Cobbley
Overhead hydro test passed
INSP-Sprinkler Rough-in/Hydro10/5/201510/5/201510/5/2015PPASS
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Sprinkler Rough-in/Hydro10/1/201510/2/201510/2/2015AFAIL
DetailsTroy Cobbley
I performed above ground hydro test twice but it failed both times due to a visible loss of pressure at the guage. It appears the aux. drain valve may be leaking.
INSP-Sprinkler Rough-in/Hydro9/22/20159/23/20159/23/2015APASS
DetailsTroy Cobbley
Piping above gridded ceilings is ok to cover.
INSP-Sprinkler Rough-in9/9/20159/10/20159/10/2015APART
DetailsTroy Cobbley
Rough-in for the overhead piping is passed as far as the installation. I noted two areas of concern which are the hvac unit ducting that penatrates the roof is obstructing the discharge of the ESFR heads in two locations, and the second area of concern is the walkway grating that exceeds 4'-0" in width (grating with accompanying support structure is 4'-5 1/2") with no sprinkler protection provided under it. Two areas have been provided protection but not the entire structure. I also noted that there is no protection under the two stairways to the mezzanine.