Permit Information
Permit NumberFIR15-00485
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3491 S TK AVE
Project NameB&D FOODS NEW MEAT PROCESSING
Customer Number 
ePlanReviewYes
Description
[B & D Foods Meat Processing]
The fire sprinkler scope of work consists of dropping pendent sprinklers into a new meat processing area. The meat processing area is apparently a freestanding metal building within the main building. In addition, a new boiler room will be protected by connecting to the end of an existing main and adding five new sprinklers. The new meat processing area is design for OHI however, the pipe sizing appears to be adequate for OH II.

Partial building scope:
(B & D FOODS INC.) Permit to construct a new 360 sq. ft. boiler room on side of existing 38,750 square foot building, to remodel the interior with new insulated wall panel and interior concrete slab to create new processing rooms and to relocate the existing exterior nitrogen tank. This permit is approved contingent upon adhering to the approved plans on file and attached engineered structural calculations. Scope of work to include plumbing, electrical, lighting and new pre manufactured wall panels. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/22/201510/23/201510/23/2015APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Final Inspection9/15/20159/15/20159/15/2015APART
DetailsJim Page
Partial fire sprinkler inspection passed/complete per this scope of work associated with this FIR permit.

The work that was submitted, approved and installed was ok. However, additional sprinklers are required to protect inside equipment and below equipment which was not shown on the drawings. A plan mod is required. TRF 9/16/2015