Permit Information
Permit NumberFIR15-00588
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 119 S 10TH ST
Project Name119 Condominiums
Customer Number 
ePlanReviewYes
Description
[10th and Grove Condos - 119 Condominiums]
The fire sprinkler scope of work consists of dry and wet systems. There are also two manual wet standpipes. The two bottom levels are design per NFPA 13 for OH. The top levels are per NFPA13 for light hazard, - 5/19/2016 TRF

Plan Mod #1 - 5/20/2016
Add protection for the attic and closets

The underground piping was approved under permit FIR15-00235

(119 Grove): Permit to construct 4 floors Type V 1-hour construction over 3-hour horizontal separation of the Type 1A two story parking garage per City of Boise Type V ordinance. This portion of the building consists of 26 units of condominium spaces on top of a two story concrete parking podium with 3-hour separation. The podium plans are currently under review as BLD14-02156. This building is required to be fire sprinklered. Separate Fire Alarm and Fire Sprinkler permits will be required; as regulated by the Fire Department.**ajs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/26/201610/28/201610/28/2016PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in/Hydro10/13/201610/13/201610/13/2016APASS
DetailsJim Page
24 hour air test for the 2 parking garage dry systems complete.
INSP-Sprinkler Rough-in10/10/201610/11/201610/11/2016PCANC
DetailsJim Page
Hydrostatic test for remaining wet systems will be rescheduled to coincide with 24 hour air est completion.
INSP-Sprinkler Rough-in/Hydro10/10/201610/11/201610/11/2016PPART
DetailsJim Page
24 hour air test for both dry systems started at 10:00AM
INSP-Sprinkler Rough-in6/9/20166/10/20166/10/2016APART
DetailsJim Page
Rough in inspection for attic system complete, attic system approved for cover.
INSP-Sprinkler Rough-in5/23/20165/24/20165/24/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located above hardlids on level 3 complete, overhead fire sprinkler piping located above hardlids on level 3 approved for cover.
INSP-Sprinkler Rough-in/Hydro5/5/20165/9/20165/9/2016PCANC
DetailsJim Page
Spoke to point of contact provided, Colton Phone #: ###-#### , inspection requests were to be cancelled and resheduled for a later date. Cancelling this inspection request based on conversation with point of contact.
INSP-Sprinkler Rough-in5/5/20165/6/20165/6/2016ACANC
DetailsJim Page
Rough to cover inspection cannot be completed at this time. Fire sprinkler plans may need to be resubmitted/approved, until this is finalized, no area's can be covered. This inspection request cancelled.
INSP-Sprinkler Rough-in/Hydro3/1/20163/2/20163/2/2016PPASS
DetailsJim Page
Hydrostatic test, 2hrs @ 200psi passed/complete for 3rd level.
INSP-Sprinkler Rough-in/Hydro2/24/20162/25/20162/25/2016PPASS
DetailsJim Page
First floor dry system hydrostatic test passed/complete.
INSP-Sprinkler Rough-in/Hydro2/23/20162/24/20162/24/2016PPART
DetailsJim Page
2nd floor dry system hydrostatic test passed/complete. 1st floor dry system hydrostatic test failed due to system leakage. will need retested at later date.
INSP-Supply line flush2/15/20162/16/20162/16/2016PCANC
DetailsJim Page
Inspection request was for underground hydro/flush, underground permit issued under FIR15-00235. Inspection request for underground flush/hydro under this FIR permit cancelled.
INSP-Sprinkler Rough-in/Hydro2/15/20162/16/20162/16/2016ACANC
DetailsJim Page
Inspection request was for underground hydro/flush, underground permit issued under FIR15-00235.
INSP-Sprinkler Rough-in1/27/20161/29/20161/29/2016PPART
DetailsJim Page
Rough in inspection complete for first floor and second floor, notated the city approved drawings with red ink/yellow high-lighter area's inspected and approved for cover. Inspected apartments on third level, high-lighted city approved drawings with yellow the sprinkler branchlines that were inspected and approved for cover.
INSP-Sprinkler Rough-in1/26/20161/27/20161/27/2016PCANC
DetailsJim Page
Spoke with point of contact Matt, phone number ###-####, requested to have the inspection rescheduled due to scheduling conflict for today. Matt said that was acceptable and will reshedule inspection request.