INSP-Final Inspection | 5/27/2016 | 5/27/2016 | 5/27/2016 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection passed/complete
|
INSP-Sprinkler Rough-in | 3/31/2016 | 4/1/2016 | 4/1/2016 | A | PASS |
Jim Page
|
|
|
Rough to cover inspection complete, all tenting for overhead fire sprinkler inspected and complete, all fire sprinkler piping approved for cover.
|
INSP-Sprinkler Rough-in | 3/30/2016 | 3/30/2016 | 3/30/2016 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for the tenting on the second level complete, second level approved for cover, will return to verify tenting is complete over the fire sprinkler piping located in the attic space above kitchen area and attic space above living room.
|
INSP-Supply line flush | 3/29/2016 | 3/30/2016 | 3/30/2016 | A | CANC |
Jim Page
|
|
|
Inspection request is for a rough to cover inspection, not a supply line flush. Cancelling this inspection request and generating a new one.
|
INSP-Sprinkler Rough-in | 3/25/2016 | 3/28/2016 | 3/28/2016 | P | PART |
Jim Page
|
|
|
Ground level fire sprinkler piping approved for cover. Fire sprinkler piping in attic area cannot be covered until fire sprinkler pipe insulation tenting is installed and inspected.
|
INSP-Sprinkler Rough-in/Hydro | 3/23/2016 | 3/25/2016 | 3/25/2016 | A | PART |
Troy Cobbley
|
|
|
Sidewall sprinkler head added for the concealed space at the fireplace per the previous correction. Sprinkler protection is required in the master shower or an 8" lintel is to be provided to create a separate compartment. No tenting has been installed so no sprinkler piping is to be covered.
|
INSP-Supply line flush | 3/23/2016 | 3/24/2016 | 3/24/2016 | A | DONE |
Jim Page
|
|
|
Underground supply flush complete
|
INSP-Supply line flush | 3/11/2016 | 3/14/2016 | 3/14/2016 | P | CANC |
Jim Page
|
|
|
Please Contact Steve Vaughn ###-#### to schedule. Phone #: ###-#### >> Inspection requested via web by Randy Knutson Inspection cancelled via mobile web on Monday, March 14, 2016.
|
INSP-Sprinkler Rough-in | 10/30/2015 | 10/30/2015 | 10/30/2015 | P | PASS |
Jim Page
|
|
|
Underground fire sprinkler supply line inspection passed/complete, approved for cover.
|