Permit NumberFIR15-00717
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 10701 W JEWELL LN
Project NameCordillera II Bldg 7
Customer Number 
ePlanReviewYes
Description
[Cordillera II Building 7]
The fire sprinkler scope of work consists of CPVC piping is being used with extended coverage residential sprinklers to protect a two level, four unit apartment building using NFPA 13R

(CORDILLERA DEVELOPMENT PHASE 2 - BLDG 7) revisons to footing calculations and 310 form. **10/8/15 ajs** To construct a new 3,680 sq. ft., two story, Four unit, apartment building. Units 'A' have one bedroom, one den, and two bathrooms. Units 'B' have two bedrooms, and two bathrooms. All 4 dwelling units have their own independent exit. All construction per the approved plans, attached plan review report, and all other reviewing agencies approvals. One-hour fire-partition separations are required between dwelling units. This building is required to be fire sprinklered. The fire sprinkler system shall be per NFPA 13R as regulated by the fire department. **AJS**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/8/20163/9/20163/9/2016APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro2/26/20162/29/20162/29/2016PPASS
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Sprinkler Rough-in/Hydro2/25/20162/26/20162/26/2016AFAIL
DetailsTroy Cobbley
Overhead hydro failed due to visible loss at guage.
INSP-Sprinkler Rough-in/Hydro2/24/20162/25/20162/25/2016PCANC
DetailsTroy Cobbley
Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Supply line flush2/24/20162/25/20162/25/2016APASS
DetailsTroy Cobbley
Supply line flush passed
INSP-Supply line flush2/10/20162/11/20162/11/2016ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in1/18/20161/19/20161/19/2016APASS
DetailsTroy Cobbley
Tenting passed. Piping can be covered.
INSP-Sprinkler Rough-in1/14/20161/15/20161/15/2016AFAIL
DetailsTroy Cobbley
Tenting has not been corrected. Do not cover piping.
INSP-Sprinkler Rough-in1/14/20161/14/20161/14/2016PPART
DetailsTroy Cobbley
Rough-in passed but tenting was incorrect. Piping can not be covered until a tenting inspection has passed.
INSP-Sprinkler Rough-in10/27/201510/28/201510/28/2015ADONE
DetailsTroy Cobbley
United water installed the short run of underground supply to riser room. Was not inspected by myself or the sprinkler contractor.