Permit Information
Permit NumberFIR15-00796
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 2266 E WALLING DR
Project NameFalling Brook Condos Bldg 4
Customer Number 
ePlanReviewYes
Description
[Falling Brook Condos Building #4]
The fire sprinkler scope of work consists of protection a 11 unit 2 level condominium. The protection is designed per NFPA13R. The system utilizes CPVC piping and extended coverage residential sprinklers.

(FALLING BROOK CONDOS – Building #4) Permit is to construct a nine unit 15,652 square foot residential apartment building with 7,696 sq. ft. on the first story and 7,956 sq. ft. on the second story. This building is to be constructed on an existing foundation. This building is fully fire sprinklered for the R2 occupancy. All units in this building are two story units and are not required to be accessible. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/27/20166/30/20166/30/2016PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete.
INSP-Final Inspection6/13/20166/13/20166/13/2016PPART
DetailsJim Page
Partial final inspection for overhead fire sprinklers complete, FIR permit for fire sprinklers cannot be finaled until fire alarm signals have been tested/verified and monitoring station has recieved signals.
INSP-Final Inspection6/8/20166/13/20166/13/2016ACANC
DetailsJim Page
Please let Jake know when you are headed out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in3/2/20163/3/20163/3/2016PPASS
DetailsJim Page
Tenting inspection for 2nd level passed/complete, overhead piping for second level approved for cover.
INSP-Supply line flush3/1/20163/3/20163/3/2016ADONE
DetailsJim Page
Underground main supply flush complete.
INSP-Sprinkler Rough-in/Hydro1/26/20161/26/20161/26/2016PPART
DetailsJim Page
2 hour hydrostatic test @ 200psi complete for overhead sprinkler piping. Rough to cover inspection complete for building 4, 1st level approved for cover, 2nd level needs tenting installed over piping in attic space, can not cover 2nd level until tenting is inspected.
INSP-Sprinkler Rough-in/Hydro1/25/20161/25/20161/25/2016PCANC
DetailsJim Page
Inspection request cancelled per conversation with Anthony, phone number ###-####, will reshedule inspection request for later date.