Permit Information
Permit NumberFIR15-00900
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 3000 S BOWN WAY
Project NameRiverwalk Condos at Bown Cross
Customer Number 
ePlanReviewYes
Description
[Riverwalk Condos at Bown Crossing]
The fire sprinkler scope of work consists of protection a three level multi-family dwelling with a NFPA 13R system

(RIVERWALK CONDOS)(BOWN CROSSING) Plan modification; change to drainage only **ajs** 11-20-15 Permit for 10 Unit Apartment complex and associated carport with surface parking on existing parking area. The NFPA 13-R fire sprinkler system is used for occupancy. To construct a 10,000 square foot three story apartment building (5,338 sq. ft. 1st story, 5,338 sq. ft. 2nd story, 1,058 sq. ft. 3rd story, the 3rd story is only available through 3 of the 2nd floor units.). All ground floor units are required to comply as Type B dwelling units. No elevator is provided in this building. Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood stud bearing walls, wood stud shear walls, fiberglass shingles, fiber-cement board siding, manufactured stone veneer, 1-hr dwelling unit separations, .75 hr (45 min) minimum fire-resistance-rated doors into the atrium with 20 minute smoke- and draft-control doors, interior nonbearing walls, millwork, and finishes. The roof truss design is a deferred submittal item. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13-R and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **ajs**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/19/20171/19/20171/19/2017PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Supply line flush1/3/20171/3/20171/3/2017PCANC
DetailsJim Page
Piping installed between underground to backflow was not the correct size, piping installed is 1 1/4 piping and the approved drawings shows an 1 1/2 supply, pipe replacement for correct size will be verified at final inspection.
INSP-Final Inspection12/29/201612/30/201612/30/2016PCANC
DetailsJim Page
Final inspection for fire sprinklers will be rescheduled for a later date.
INSP-Supply line flush12/29/201612/30/201612/30/2016ADONE
DetailsJim Page
Underground supply flush complete.
INSP-Supply line flush9/8/20169/9/20169/9/2016AFAIL
DetailsJim Page
Flush will need to be performed again, something is obstructing the flow, piping will need to be repaired and flush rescheduled.
INSP-Sprinkler Rough-in8/25/20168/26/20168/26/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover.
INSP-Supply line flush8/4/20168/5/20168/5/2016AFAIL
DetailsJim Page
Could not verify if fire line is connected or not, flush could not be accomplished.
INSP-Sprinkler Rough-in/Hydro7/25/20167/25/20167/25/2016PPASS
DetailsJim Page
Hydrostatic test for level 1 overhead fire sprinkler piping complete.
INSP-Sprinkler Rough-in7/20/20167/20/20167/20/2016PPART
DetailsJim Page
Hydrostatic test complete for level 2 and level 3 overhead fire sprinkler piping. Overhead fire sprinkler piping on level 1 approved for cover. Overhead fire sprinkler piping that is between level 2 and level 3 living area's approved for cover. Fire sprinkler piping that is located between the roof deck & livings area's on level 2 and level 3 cannot be covered until a tenting inspection has been completed. Any piping in these area's that gets covered before tenting inspection is complete will have cover material removed to verify that tenting insulation has been installed..