Permit NumberFIR16-00086
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY
Site Address 1215 W STATE ST
Project NameIT Clean Agent Suppression
Customer Number 
ePlanReviewYes
Description
[Idaho State Insurance Fund]
The fire protection scope of work consists of clean agent system for the server room. A new Sapphire clean agent suppression system utilizing Novec 1230 fluid will be installed per NFPA 2001 and manufacturers specifications.

There does not seem to be an associated building permit at this time.

Note: The clean agent system does not remove the requirement for fire sprinklers (if any) in the data center, if the building is a fully sprinklered building. Fire sprinklers are still required. A gaseous system may be used below the raise floor (if any). (Ref: NFPA 13: 22.14.2.1 and 22.14.2.3)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/30/201612/30/201612/30/2016APASS
DetailsJim Page
Final inspection for clean agent fire panel interface to existing fire alarm panel passed/complete, permit finaled.
INSP-Final Inspection4/19/20164/22/20164/22/2016APART
DetailsJim Page
Partial final inspection of clean agent alarm panel/clean agent release complete. All devices associated with clean agent fire alarms/tank activation tested, all devices that were tested passed inspection. Clean agent fire panel is not connected to the buildings main fire alarm system, clean agent fire panel needs to be monitored by the buildings main fire alarm panel (any modifications to the buildings fire alarm system will require a seperate FIR permit issued before work can be performed). A follow up inspection will need to be scheduled after interface between clean agent and main fire panel are complete. Once the panel interface is complete and inspected this FIR permit can be completed.
INSP-Final Inspection4/12/20164/19/20164/19/2016PCANC
DetailsJim Page
Inspection request cancelled due to scheduling issue, inspection request will be rescheduled for a later date.