Permit Information
Permit NumberFIR16-00088
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 611 S 8TH ST
Project NameThe Afton Condominiums
Customer Number 
ePlanReviewYes
Description
[The Afton]
The fire sprinkler scope of work consists of a 400 Gpm @ 70 Psi fire pump, two manual wet standpipes, two dry systems, seven wet systems and floor control valves in a six level building with a penthouse. There are live/work units, two levels of parking garage, a garden shed and condominiums. This building is protected per NFPA 13. There is concealed CPVC piping. All exposed piping is steel. This building is not considered a high-rise.

The underground permit is under FIR15-00838


(THE AFTON CONDOMINIUMS – PHASE II) (DRH14-00262) The fire sprinkler system (NFPA 13 below, next to, and above the podium per the “Special Design Standards for Type V Construction” ordinance) will be used for story and height increase. Grading was done under permit GRD15-00067. Phase I (two story concrete podium shell) was constructed under permit BLD15-03329. To construct a 3 story Type V-A apartment building having 3 one story dwelling units and 3 two story dwelling units next to the Type I-A podium building (about 2,533 square feet per story or 7,600 square feet for the building). To construct a 4 story Type V-A apartment building on top of the Type I-A podium building. Each story will have a floor area of about 9,545 square feet (38,180 square feet for the building). A common assembly area, one sleeping unit, and 4 one story dwelling units will be provided on the podium level. Five one story dwelling units will be provided on the 4th, 5th, and 6th stories each (15 total). Work is to include interior and exterior 1-hr fire-resistance-rated wood bearing walls, interior 1-hr fire-resistance-rated wood dwelling unit separation walls, 1-hr fire-resistance-rated wood floor-ceiling and roof-ceiling assemblies, a 2-hr fire-resistance-rated fire barrier wall above the 3-hr podium to function as a horizontal exit, interior nonbearing wood walls, interior doors, exterior doors and windows, exterior wall finishes, open egress balconies, a 1-hr fire-resistance-rated corridor, a 2-hr fire-resistance-rated elevator shaft, an elevator, two full height 2-hr fire-resistance-rated stairway exit enclosures with one extending to and serving the roof, millwork, restrooms, and interior finishes. All dwelling units are required to comply as Type B dwelling units, with at least one also complying as a Type A dwelling unit. The sleeping unit is required to comply as an accessible unit. To create storage areas, three two story live/work units, a two story lobby to serve the upper apartments, a shell retail sales tenant space with a high ceiling, and a two story enclosed parking garage within the Type I-A podium building on the 1st and 2nd stories. Work is to include stairways to serve 2nd stories, 1-hr fire-resistance-rated non-combustible dwelling unit separation walls, interior noncombustible walls, restrooms, interior doors, exterior doors and windows, exterior wall finishes, millwork, and interior finishes. Special Inspection is required for structural steel, welding, structural wood panel shear walls, wood floor and roof diaphragms, and masonry. Structural Observation by the Engineer of Record is required. Deferred submittal items include engineered wood trusses. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/21/20178/22/20178/22/2017APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Final Inspection6/13/20176/15/20176/15/2017APART
DetailsJim Page
Partial final inspection for fire sprinklers complete. Main building as well as parking garages complete, town homes will have final inspection requested at a later date (General contractor is requesting TCO for main building untis and parking garage levels including lobbies on both 1st and 2nd, town homes to be completed at a later date)
INSP-Sprinkler Rough-in5/24/20175/31/20176/2/2017APASS
DetailsJim Page
Fire pump start up complete
INSP-Sprinkler Rough-in/Hydro6/1/20176/1/20176/1/2017PPASS
DetailsJim Page
Hydrostatic test complete for entire building.
INSP-Sprinkler Rough-in/Hydro5/24/20175/26/20175/26/2017APASS
DetailsJim Page
Underground re-hydro tested due to developed leak from seperate contractor impacting thrust block. Restraints have been installed to protect underground from seperation due to site work and underground re-hydro complete.
INSP-Sprinkler Rough-in/Hydro5/17/20175/17/20175/17/2017PPASS
DetailsJim Page
24 hour air test on both dry systems complete
INSP-Sprinkler Rough-in/Hydro5/16/20175/16/20175/16/2017PPART
DetailsJim Page
24 hour air test on both dry systems started at 10:20AM with 49 PSI on both systems.
INSP-Sprinkler Rough-in/Hydro4/24/20174/24/20174/24/2017PPART
DetailsJim Page
Hydrostatic test complete for garage dry systems (level 1 and 2 dry systems), stand pipe and overhead fire sprinkler piping in townhomes.
INSP-Sprinkler Rough-in4/11/20174/12/20174/12/2017APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping in the outside soffit on northeast corner complete, approved for cover.
INSP-Sprinkler Rough-in3/28/20173/29/20173/29/2017APART
DetailsJim Page
Rough to cover inspection for fire sprinkler piping/pendant heads in lobby area complete, approved for cover.
INSP-Sprinkler Rough-in/Hydro3/28/20173/29/20173/28/2017PCANC
DetailsJim Page
Hydro on town homes rough to cover on lobby. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in2/10/20172/15/20172/15/2017APART
DetailsJim Page
Rough to cover inspection for west side cottages complete to include tenting for sprinkler piping in attic space, overhead fire sprinkler piping in cottages approved for cover.
INSP-Sprinkler Rough-in1/13/20171/13/20171/13/2017PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping in the condo units on level 2 complete, approved for cover. Cottages on the west side still need to have rough to cover inspection performed before fire sprinkler piping can be covered.
INSP-Sprinkler Rough-in12/29/201612/30/201612/30/2016AFAIL
DetailsJim Page
Overhead fire sprinkler piping on level 6 cannot be covered, every apartment on level 6 has piping that is completely covered with insulation, a clear pocket needs to be maintained between all overhead fire sprinkler piping and the sheetrock, tenting will need to be re-inspected
INSP-Sprinkler Rough-in12/20/201612/21/201612/21/2016PDONE
DetailsJim Page
Request was for a conference, discussed tenting options with project superintendent to keep insulation on top of piping, also to maintain open space pocket between piping and vapor barrier/sheetrock for radiant heat to reach the piping.
INSP-Sprinkler Rough-in12/14/201612/15/201612/15/2016APART
DetailsJim Page
Soffit inspection for level 5 complete, soffit's approved for cover. Tenting will require modifications before cover will be approved.
INSP-Sprinkler Rough-in11/30/201611/30/201611/30/2016PPASS
DetailsKatie Marron
4th floor soffit/drops ok to cover.

Except first condo which was not ready.

Discussed soffit with cabinets and to treat the cabinet face as the 'wall', width is then 10" and no under soffit sprinklers required.
INSP-Sprinkler Rough-in11/8/201611/9/201611/9/2016PPASS
DetailsKatie Marron
Rough to cover on 6th floor. Dwelling units Ok to cover except connections to riser and trash shute loop.

Dry pendants were in but need to be adjusted so that deflectors are level.

From last inspection, Rm 302 requires additional sprinkler at upper ceiling. This was corrected ahead of time for the corrresponding room on the 6th floor.
INSP-Sprinkler Rough-in10/28/201610/31/201610/31/2016ADONE
DetailsKatie Marron
Third Floor Soffits inspected (except community space).
- Soffit over 30' requires a sprinkler under in living room unit 304
-Unit 302 bedroom has sprinkler installed under soffit. Contractor to verify one is not required in ceiling pocket (ie meets exceptions of 8.10.8.2)
INSP-Sprinkler Rough-in10/7/201610/7/201610/7/2016PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping on level 5 complete, overhead fire sprinkler piping on level 5 approved for cover.
INSP-Sprinkler Rough-in9/19/20169/20/20169/20/2016APASS
DetailsJim Page
Rough to cover inspectio for overhead fire sprinkler piping on level 4 complete, overhead fire sprinkler piping on level 4 approved for cover. Informed job site superintendent to watch the insulation above metal channel, detail on fire sprinkler city approved drawings specifies how the insulation needs to be installed above the metal channel. Inspection for remaining overhead fire sprinkler piping located on level 3 complete, all overhead fire sprinkler piping located on level 3 approved for cover.
INSP-Supply line flush9/12/20169/13/20169/13/2016ADONE
DetailsJim Page
Underground fire sprinkler main supply flush complete
INSP-Sprinkler Rough-in/Hydro9/9/20169/9/20169/9/2016APASS
DetailsJim Page
200 psi hydrostatic test complete for underground main supply.
INSP-Sprinkler Rough-in8/30/20169/1/20169/1/2016PPART
DetailsJim Page
Partial rough to cover inspection complete for foverhead fire sprinkler piping located on levels 1, 2 and 3, notated city approved drawings with blue highlighter/red ink overhead fire sprinkler piping approved for cover.
INSP-Sprinkler Rough-in7/12/20167/12/20167/12/2016PPASS
DetailsJim Page
Underground rough to cover inspection complete, underground approved for cover.