Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR16-00143
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1055 N CURTIS RD
Project NameST. ALS CT#3 1ST FLOOR T.I.
Customer Number 
ePlanReviewYes
Description
[Saint Al's CT Scan Area] - Quick Permit
Add, plug and relocate sprinklers to accommodate new wall and ceiling configuration.

(ST ALPHONSUS CT SCAN AREA – 1ST STORY – SOUTH TOWER) Fire sprinkler system is required because this is a high-rise building. To remodel the existing 1,235 square foot CT scan area located on the 1st story near the center of the South side of the South Tower. Work is to include a restroom accessible to the disabled, interior nonbearing walls, interior windows, lead shielding, interior doors, millwork, and finishes. Except for a new door in an existing smoke partition, no fire barriers, smoke barriers, or smoke partitions are affected by this remodel. A new doorway will be created in an existing masonry wall that is also a smoke partition (i.e. I-2 corridor). Steel headers and jambs will be installed. Adequate gravity load transfer is required and shall be verified. An existing opening in the same wall will be filled in. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/1/20167/1/20167/1/2016APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in6/22/20166/23/20166/23/2016APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinklers complete, notated city approved drawings area's approved for cover.
INSP-Sprinkler Rough-in4/19/20164/19/20164/19/2016PPASS
DetailsTroy Cobbley
See the city approved plans for location where piping can be covered with todays date.
INSP-Sprinkler Rough-in3/28/20163/29/20163/29/2016APASS
DetailsTroy Cobbley
The two pendant heads located in the soffit are ok to cover.