Permit Information
Permit NumberFIR16-00194
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 505 W BROAD STREET
Project NameThe Fowler Project
Customer Number 
ePlanReviewYes
Description
[The Fowler]
The fire sprinkler scope of work consists of a 1000 Gpm @ 110 Psi fire pump, three Class I automatic wet standpipes, two dry systems, two wet systems for podium 1st & 2nd floor levels. The 3rd - 7th floors are deferred submittal. Some of the mains are required to be heat traced and insulated. There are retail areas on the first floor. Stair tower one has a combination standpipe with floor control valves. There is a horizontal exit with additional standpipe outlets.

The underground was reviewed under permit FIR16-00116
(THE FOWLER – Core Area Build Out – Below Podium Structure) **GREEN TAG-Expedited Review-LEED Project - PROJECT MANAGEMENT-Angie Brosious**Permit to build out a new 68,730 square foot (2) story shell building originally constructed under BLD15-02043. The first floor is around 34,000 square feet and the second floor is around 34,730 square feet. This building is fully fire sprinklered with an NFPA 13 system to comply with the 5 story wood construction ordinance. Scope of work includes: [installation of interior non-bearing walls and bearing walls to create 5 live/work units, four future tenant spaces on the first floor, and accessory office / residential amenity rooms on the second floor], new plumbing, new electrical, new mechanical, new insulation, new windows, new doors, and interior finishes in compliance with Chapter 8 of the 2012 IBC. NOTE: the tenant spaces on the first floor are not allowed occupancy until a separate permit is pulled to remodel and occupy those spaces. This building will be sprinklered with a fully compliant NFPA 13 system to comply with the 5 story wood construction ordinance. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/28/20183/1/20183/1/2018APASS
DetailsJim Page
Final fire sprinkler inspection complete.
INSP-Final Inspection2/15/20182/15/20182/15/2018PPART
DetailsJim Page
Final fire sprinkler inspection for levels 3 and 4 complete.
INSP-Final Inspection2/5/20182/6/20182/6/2018APART
DetailsJim Page
Final fire sprinkler inspection for levels 5 and 6 complete.
INSP-Final Inspection1/15/20181/16/20181/16/2018APART
DetailsJim Page
Final fire sprinkler inspection for level 7 complete.
INSP-Sprinkler Rough-in12/11/201712/12/201712/12/2017APART
DetailsJim Page
Rough to cover inspection for live work area of first floor complete, approved for cover.
INSP-Sprinkler Rough-in/Hydro10/17/201710/18/201710/18/2017ACANC
DetailsJim Page
We will have it pumped up around ten am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in/Hydro9/18/20179/20/20179/20/2017APASS
DetailsJim Page
24 hour air test complete for levels 1 and 2 dry systems.
INSP-Sprinkler Rough-in9/20/20179/20/20179/20/2017APART
DetailsJim Page
Fire pump start up/commissioning complete. All tamper switches and flow switches in fire pump room complete. Final inspection for tampers and flows on level 1 and 2 wet systems complete.
INSP-Alarm Testing9/19/20179/20/20179/20/2017ACANC
DetailsJim Page
Pump test at nine am. Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in/Hydro9/18/20179/19/20179/19/2017APART
DetailsJim Page
24 hour air test started at 0845 on 19SEPT2017, level 1 dry system at 43 psi, level 2 dry system at 42 psi
INSP-Sprinkler Rough-in/Hydro9/18/20179/20/20179/18/2017ACANC
DetailsJim Page
Finish 24 hour air test on first floor dry system Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in/Hydro9/18/20179/19/20179/18/2017ACANC
DetailsJim Page
24 hour air test Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in/Hydro9/14/20179/15/20179/15/2017APART
DetailsJim Page
Hydrostatic test for level 1 dry system complete
INSP-Alarm Testing9/13/20179/14/20179/14/2017APART
DetailsTroy Cobbley
Could not test the fire alarm interconnections due to most of them not being shown on the fire alarm plans. Also appears flow switches and tamper switches have been deleted in the stairwells.
What I was able to do today was trip test both of the dry systems. The first floor had water at the inspectors test in 49 seconds and the second floor was 32 seconds.
INSP-Sprinkler Rough-in/Hydro9/1/20179/5/20179/5/2017APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping on level 2 wet system complete, level 2 wet system approved for cover. Hydrostatic test for level 1 and 2 wet systems complete. Hydrostatic test for level 2 dry system complete.
INSP-Sprinkler Rough-in/Hydro8/29/20178/30/20178/30/2017APASS
DetailsJim Page
Hydrostatic test for three standpipes complete.
INSP-Conference7/27/20177/27/20177/27/2017ADONE
DetailsJim Page
Fire conference was for fire pump room access and egress, it is determined that the access to the fire pump room is adequate, no changes need to be made to current piping configuration on backflow preventer configuration. (Conference was with the Building Inspector Dave Hannah, Fire Inspector Supervisor Scott Arellano as well as installing contractor, Sam Ball)
INSP-Sprinkler Rough-in/Hydro4/25/20164/25/20164/25/2016PPASS
DetailsJim Page
Underground hydrostatic test passed/complete