Permit Information
Permit NumberFIR16-00234
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 9095 S FEDERAL WAY Unit: 200
Project NameTEL TOYKO TI STE 200
Customer Number 
ePlanReviewYes
Description
[Tokyo Electronics]
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration.

(TOKYO ELECTRONICS) Permit for first time tenant improvements to an existing 4,957 sq. ft. tenant space on the second story of an existing 26,000 sq. ft. building with work to include the construction of new interior nonbearing partition walls to create new offices, conference rooms a workout room and restroom/shower rooms per the approved plans. This building is fully fire sprinklered for story increase. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/22/20167/26/20167/26/2016APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in7/7/20167/8/20167/8/2016PPASS
DetailsJim Page
Rough to cover inspection fore overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover.
INSP-Sprinkler Rough-in4/27/20164/27/20164/27/2016PPASS
DetailsJim Page
Previously noted items above restroom hardlids addressed, pendeant head in mens room relocated for proper spacing, upright head added to cover exposed combustible material that is attached to restroom ceiling joist. Overhead fire sprinkler piping above restroom hardlids approved for cover.
INSP-Sprinkler Rough-in4/26/20164/26/20164/26/2016PFAIL
DetailsJim Page
Female restroom approved for cover, notated with red in on city approved plans heads that are okay to cover. First head in mens restroom not approved for cover, mens restroom sprinkler head scales at 9 foot off of wall on city approved drawings, sprinkler head is installed 10ft 5in off of wall, head needs to be relocated. 4X8 foot sheet of plywood is attached to ceiling joists above mens restroom, no upright protection for that area, combustible material needs to either be fire rated/treated, removed or upright protection installed for combustible material.