Permit Information
Permit NumberFIR16-00266
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7466 W SAXTON DR
Project NameKensington Apartments Bldg P
Customer Number 
ePlanReviewYes
Description
Thorpe Fire Sprinkler Systems to install a new NFPA 13R fire sprinkler system and dry-manual standpipe system in this new 4 story apartment building. Underground for this building is on a separate permit: #FIR15-00689
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/13/201612/13/201612/13/2016PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Alarm Testing12/13/201612/13/201612/13/2016PCANC
DetailsJim Page
Inspection request is for a final inspection on fire sprinklers, this inspection request cancelled and a new one will be generated.
INSP-Final Inspection12/5/201612/6/201612/6/2016PPART
DetailsJim Page
Partial final complete for overhead fire sprinkler system. Tampers and flow switches will be inspected during alarm inspection, heat chase was being installed for piping crossing the breezeway at time of this inspection. Chase heat for sprinkler piping will be verified during alarm/life safety inspection.
INSP-Sprinkler Rough-in8/1/20168/1/20168/1/2016PPASS
DetailsJim Page
Tenting inspection for overhead fire sprinkler piping located in attic area's complete, overhead fire sprinkler piping located in attic spaces approved for cover. Only area's not approved for cover are where the fire sprinkler piping crosses the breeze-way, an approved method to prevent the pipe from freezing needs to be install/inspected before cover is approved. Any of the area's where the fire sprinkler piping crosses the breeze-way that gets covered before approved for cover will have any and all cover material removed for an inspection to be performed.
INSP-Sprinkler Rough-in7/25/20167/26/20167/26/2016AFAIL
DetailsJim Page
Tenting insulation for overhead fire sprinkler piping located in attic spaces not installed, only plastic sheeting installed, noted in fire sprinkler review notes under general requirements, section 10: "A minimum of R38 of insulation is required on top of the piping per the IEC." Overhead fire sprinkler piping located in attic spaces not approved for cover.
INSP-Sprinkler Rough-in/Hydro7/19/20167/21/20167/21/2016APASS
DetailsJim Page
Hydrostatic test complete for levels 1, 2, 3 and 4 overhead fire sprinkler piping. Overhead fire sprinkler piping that is not in attic space is approved for cover, overhead fire sprinkler piping located in attic spaces cannot be covered until tenting insulation inspection is complete, overhead fire sprinkler piping that gets covered before tenting inspection is completed will have any and all cover removed for tenting inspection.
INSP-Supply line flush7/20/20167/21/20167/21/2016APASS
DetailsJim Page
Inspection request was for underground hydrostatic test and underground rough to cover, not a flush. Underground hydrostatic test passed/complete, underground supply approved for cover, flush will be completed at a later date.
INSP-Sprinkler Rough-in/Hydro7/7/20167/8/20167/8/2016PPASS
DetailsJim Page
200 psi hydrostatic test complete for standpipe.