INSP-Final Inspection | 1/16/2018 | 1/17/2018 | 1/17/2018 | P | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection for area of work complete.
|
INSP-Final Inspection | 10/9/2017 | 10/9/2017 | 10/9/2017 | A | PART |
Jim Page
|
|
|
Final fire sprinkler inspection complete, permit will remain in issued status until completion of the project.
|
INSP-Sprinkler Rough-in/Hydro | 9/26/2017 | 9/27/2017 | 9/27/2017 | P | PASS |
Jim Page
|
|
|
Hydrostatic test for level 8 complete
|
INSP-Sprinkler Rough-in/Hydro | 9/27/2017 | 9/27/2017 | 9/27/2017 | A | PART |
Jim Page
|
|
|
Hydrostatic test for level 1 wet system complete
|
INSP-Final Inspection | 9/26/2017 | 9/27/2017 | 9/27/2017 | A | CANC |
Jim Page
|
|
|
Inspection for level 1 hydro, final inspection to be completed at a later date, this request is cancelled.
|
INSP-Sprinkler Rough-in/Hydro | 9/26/2017 | 9/27/2017 | 9/26/2017 | A | CANC |
Jim Page
|
|
|
Contact Ken Orahood ###-#### 30 min prior to Fire Final Insp start please Final 1st floor Wet system Hydro 1st floor Wet system sched for Afternoon Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 9/22/2017 | 9/25/2017 | 9/25/2017 | P | PART |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping complete for level 9 and 10.
|
INSP-Sprinkler Rough-in/Hydro | 9/18/2017 | 9/19/2017 | 9/19/2017 | A | CANC |
Jim Page
|
|
|
Inspection request was for fire pump start up, fire pump is under FIR16-00090, this request is cancelled.
|
INSP-Sprinkler Rough-in | 8/4/2017 | 8/7/2017 | 8/7/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads complete for 3rd floor corridor as well as 4th floor 02 room, inspected area's approved for cover.
|
INSP-Sprinkler Rough-in | 8/1/2017 | 8/1/2017 | 8/1/2017 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in floors 5,6,7 ; 8 number 02 bedrooms complete (Rooms that were completed after construction elevator was removed) approved for cover.
|
INSP-Conference | 7/13/2017 | 7/14/2017 | 7/14/2017 | A | DONE |
Jim Page
|
|
|
Fire conference complete
|
INSP-Sprinkler Rough-in | 7/3/2017 | 7/6/2017 | 7/6/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads for the Laundry Chute, 10th floor conference room complete, approved for cover. Inspection request was also for fire pump commissioning, I stopped the fire pump commissioning, no water was flowed due to erosion issues (no curbing, loose dirt that would have been washed out, nearest storm drain was downstream from a dirt pile)
|
INSP-Sprinkler Rough-in | 6/22/2017 | 6/23/2017 | 6/23/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads located in the corridors on 4th-8th floors complete, approved for cover, pool area and rooms attached to pool area approved for cover.
|
INSP-Sprinkler Rough-in | 6/22/2017 | 6/22/2017 | 6/22/2017 | P | CANC |
Jim Page
|
|
|
Inspection request rescheduled for 23JUNE2017
|
INSP-Sprinkler Rough-in | 6/22/2017 | 6/22/2017 | 6/22/2017 | P | CANC |
Jim Page
|
|
|
3rd Floor pool arePls call 30 mins prior Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Conference | 6/8/2017 | 6/12/2017 | 6/12/2017 | A | DONE |
Jim Page
|
|
|
Fire conference complete, current configuration of fire sprinkler heads in studio A apartment rooms is adequate, no changes necessary.
|
INSP-Sprinkler Rough-in | 5/23/2017 | 5/24/2017 | 5/24/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads on the northwest side level 3 conference room, corridors and restrooms complete, approved for cover.
|
INSP-Sprinkler Rough-in | 5/16/2017 | 5/17/2017 | 5/17/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 10 complete, hotel resident rooms on level 10 approved for cover.
|
INSP-Sprinkler Rough-in | 4/27/2017 | 5/1/2017 | 5/1/2017 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads located in level 1 lobby complete, approved for cover.
|
INSP-Sprinkler Rough-in | 4/25/2017 | 4/26/2017 | 4/26/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 9 complete, hotel resident rooms on level 9 approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 4/7/2017 | 4/10/2017 | 4/10/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 8 complete, hotel resident rooms on level 8 approved for cover. Rough in inspection complete for level 9, rough to cover inspection will be scheduled when pendant heads are installed.
|
INSP-Sprinkler Rough-in/Hydro | 3/30/2017 | 4/3/2017 | 4/3/2017 | P | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 7 complete, hotel resident rooms on level 7 approved for cover. Hydrostatic test complete for supply from pump room to floor control valves complete as well as overhead fire sprinkler piping on levels 3, 5, 6 and 7.
|
INSP-Sprinkler Rough-in/Hydro | 3/29/2017 | 3/30/2017 | 3/30/2017 | A | CANC |
Jim Page
|
|
|
Contact will be Ken Orahood - Needing Hydro inspections for 3rd, 5th, 6th, 7th floors, RTC for 7th floor and Hydro for 8" & 6" Mains.... Questions please let us know... Thanks Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in | 3/14/2017 | 3/16/2017 | 3/16/2017 | A | PART |
Jim Page
|
|
|
Rough in inspection for overhead fire sprinkler piping on level 8 complete. Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel tenant rooms on level 6 complete, hotel tenant rooms approved for cover.
|
INSP-Sprinkler Rough-in | 3/14/2017 | 3/16/2017 | 3/14/2017 | A | CANC |
Jim Page
|
|
|
Inspection is for the 6th Floor Contact is Ken Orahood ###-#### Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in | 3/1/2017 | 3/2/2017 | 3/2/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 5 complete, hotel resident rooms on level 5 approved for cover.
|
INSP-Conference | 3/2/2017 | 3/2/2017 | 3/2/2017 | A | DONE |
Jim Page
|
|
|
Temporary standpipe for fire department use partially complete, contractor has hose valves on order, when valves are recieved they will installed with the FDC hookup.
|
INSP-Sprinkler Rough-in/Hydro | 3/1/2017 | 3/2/2017 | 3/2/2017 | A | PART |
Jim Page
|
|
|
Hydrostatic test for the level 4 complete.
|
INSP-Sprinkler Rough-in | 2/22/2017 | 2/24/2017 | 2/24/2017 | A | PART |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel rooms on level 3 complete (public common area's will need inspected after pendant heads are installed at a later date). Hotel rooms approved for cover on level 3.
|
INSP-Sprinkler Rough-in | 2/16/2017 | 2/17/2017 | 2/17/2017 | A | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel rooms on level 4 complete, hotel rooms on level 4 approved for cover.
|
INSP-Sprinkler Rough-in | 2/16/2017 | 2/21/2017 | 2/16/2017 | A | CANC |
Jim Page
|
|
|
Contact will be Ken Orahood please contact him 30 minutes before Inspection Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in | 2/1/2017 | 2/3/2017 | 2/3/2017 | A | PART |
Jim Page
|
|
|
Rough in inspection complete for levels 6 and 7, a rough to cover inspection will need to be performed after finish heads are cut before cover can be approved.
|
INSP-Sprinkler Rough-in | 12/8/2016 | 12/9/2016 | 12/9/2016 | A | PART |
Jim Page
|
|
|
Rough in inspection complete for installed overhead fire sprinkler piping (wet systems only) complete for levels 1, 3, 4 and 5. A rough to cover inspection will need to be completed before cover.
|
INSP-Sprinkler Rough-in | 12/7/2016 | 12/8/2016 | 12/8/2016 | A | CANC |
Troy Cobbley
|
|
|
To be rescheduled for tomorrow morning per Jim and Perly
|
INSP-Sprinkler Rough-in | 12/6/2016 | 12/7/2016 | 12/7/2016 | A | CANC |
Jim Page
|
|
|
Contact is Perly Daniels - RTC for Floors 1 thru 5 Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|