Permit Information
Permit NumberFIR16-00510
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7776 W SAXTON DR
Project NameKENSINGTON APARTMENTS BLDG W
Customer Number 
ePlanReviewYes
Description
[Kensington Apartments - Building W]
The fire sprinkler scope of work consists of a NFPA 13R system for a four level apartment building. The system is supplied by 2” underground through a 2” backflow preventer to (4) 2” risers. There are floor level control valves in a valve house. The system piping is CPVC with extended coverage residential sprinklers.

There is a 6” standpipe with (4) 6” risers. Each standpipe riser has (3) hose valves. The FDC is connected to the standpipe per the fire marshal’s office. Each riser has a supervised sectional control valve. The fire marshal’s office has allowed the fire apparatus to supply 1000 Gpm in lieu of the 750 Gpm stated in the Boise Policy.

[BLD15-01117] - The drawings for site work (civil, landscaping, lawn sprinklers, site electrical, site plumbing, etc.) are filed under BLD15-01107 in ePlanReview. The NFPA 13-R fire sprinkler system is used for occupancy and for story increase. To construct a 42,997 square foot four story apartment building (10,993 sq. ft. 1st story with four 2.a units and four 3.a units, 10,993 sq. ft. 2nd story with four 2.a units and four 3.a units, 10,993 sq. ft. 3rd story with four 2.a units and four 3.a units, and 10,018 sq. ft. 4th story with four 2.a units and four 2.b units). All ground floor units are required to comply as Type B dwelling units. No elevator is provided in this building. Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood stud bearing walls, wood stud shear walls, fiberglass shingles, fiber-cement board siding, manufactured stone veneer, 1-hr dwelling unit separations, .5-hr minimum fire-resistance-rated corridors with 20-minute smoke- and draft-control doors, exterior exit stairways fire rated like the corridors, steel stairways with concrete treads, interior nonbearing walls, millwork, and finishes. Special Inspection is required for soils and for concrete. The roof truss design is a deferred submittal item. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13-R and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/31/20174/3/20174/3/2017APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Final Inspection3/30/20173/31/20173/31/2017PCANC
DetailsJim Page
Inspection request rescheduled for 8AM, 03APR2017
INSP-Supply line flush3/27/20173/28/20173/28/2017PDONE
DetailsJim Page
Underground main line flush completed
INSP-Sprinkler Rough-in/Hydro3/17/20173/17/20173/17/2017PPASS
DetailsJim Page
Underground hydro complete
INSP-Sprinkler Rough-in3/17/20173/17/20173/17/2017PPASS
DetailsJim Page
Rough to cover inspection for underground supply complete, approved for cover.
INSP-Supply line flush3/17/20173/17/20173/17/2017PCANC
DetailsJim Page
INSP-Supply line flush3/15/20173/16/20173/16/2017ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact Jake Phone #: ###-#### due to complications, request will be reschedule.
INSP-Sprinkler Rough-in/Hydro1/11/20171/12/20171/12/2017ACANC
DetailsJim Page
Level 2 hydro completed on 11JAN2017
INSP-Sprinkler Rough-in/Hydro1/10/20171/11/20171/11/2017PPASS
DetailsJim Page
Hydrostatic test complete for standpip. Hydrostatic test complete for overhead fire sprinkler piping on levels 1 and 2.
INSP-Sprinkler Rough-in/Hydro12/30/20161/4/20171/4/2017PPART
DetailsJim Page
Rough to cover ispection for overhead fire sprinkler piping on levels 1 and 2 complete, approved for cover, hydrostatic test will be completed at a later date.
INSP-Sprinkler Rough-in1/3/20171/3/20171/3/2017PPASS
DetailsJim Page
Tenting inspection for level 3 fire sprinkler piping in attic spaces complete, approved for cover.
INSP-Sprinkler Rough-in/Hydro12/29/201612/30/201612/30/2016PCANC
DetailsJim Page
Hydrostatic test cancelled by point of contact due to weather conditions.
INSP-Sprinkler Rough-in/Hydro12/22/201612/23/201612/23/2016PCANC
DetailsJim Page
Inspection request cancelled per conversation with Anthony due to weahter conditions, inspection request will be rescheduled.
INSP-Sprinkler Rough-in/Hydro12/21/201612/22/201612/22/2016PCANC
DetailsJim Page
First and second floors, and standpipes. Call Anthony when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro12/20/201612/20/201612/20/2016PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete for levels 3 and 4, all overhead fire sprinkler piping on level 4 approved for cover, will need to verify heat for breezeway crossings at a later date, overhead fire sprinkler piping located between floor levels on level 3 approved for cover, tenting was not installed over piping in attic space on level 3 so piping located in attic space on level 3 cannot be covered until tenting is installed and inspected. Hydrostatic test for overhead fire sprinkler piping on levels 3 and 4 passed/complete.
INSP-Sprinkler Rough-in/Hydro12/16/201612/19/201612/19/2016ACANC
DetailsJim Page
Tenting is not completely installed over the top of overhead fire sprinkler piping. Piping cannot be covered until tenting is complete, inspection request cancelled per conversation with contractor.