Permit Information
Permit NumberFIR16-00556
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1401 W IDAHO ST
Project NameWATER COOLER APARTMENTS
Customer Number 
ePlanReviewYes
Description
[The Watercooler Apartments]
The fire sprinkler scope of work consists of protecting a three level building using a NFPA 13R wet system. The bottom level has live/work units. The units are designed per NFPA 13 for OH 2 due to the possibility of mercantile use. The bottom level also has some storage areas and a future space which will be treated as OH 2 for mercantile use. The upper levels utilize CPVC piping and residential sprinklers, the bottom level has some exposed steel piping with quick response sprinklers. The upper most level will be tented and shall have a minimum of R38 insulation on top of the piping per IEC.

The underground piping is under permit FIR16-00449

[BLD16-00473] - The NFPA 13R fire sprinkler system is used for the R-2 Occupancy. To construct a 34,716 square foot apartment building (11,502 square feet 1st story, 11,609 square feet 2nd story, and 11,605 square feet 3rd story). The 2nd and 3rd stories will have 15 single story dwelling units each. The 1st story will have 6 one story live-work units each having a mezzanine and 1 single story Type A dwelling unit without a mezzanine. All 1st story units are required to comply as Type B dwelling units. Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood bearing walls, wood exterior walls, wood floors, wood roof, exterior doors, exterior windows, exterior tongue & grove cedar siding wall finish, exterior stucco wall finish, exterior stucco soffits, roof coverings, interior doors, millwork, and finishes. Special Inspection is required for concrete, welding, bolting, soils, wind resistance, seismic resistance, and for fire-stopping. Engineered fill is required. Seven-foot-tall green walls will be provided at grade. Deferred submittals include engineered wood trusses. This permit does not establish a Certificate of Occupancy for the commercial shell space. A separate permit is required to establish occupancy for that space. Before a live-work unit is allowed to be used for any commercial use, a separate permit is required to establish occupancy for that unit. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13R and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW** --TRF--
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/12/20177/13/20177/13/2017APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Sprinkler Rough-in5/30/20175/31/20175/31/2017APASS
DetailsScott Arellano
Fire sprinkler main heat traced and will be insulated at east side unheated area, access hatch provided, monitoring module installed. Testing of module will take place at fire alarm inspection. Ok to cover.
INSP-Sprinkler Rough-in5/24/20175/25/20175/25/2017APART
DetailsJim Page
Rough to cover inspection for tenting on pod 3 complete, approved for cover.
INSP-Sprinkler Rough-in5/8/20175/9/20175/9/2017APART
DetailsJim Page
Rough to cover inspection for tenting on pod 4 complete, approved for cover.
INSP-Sprinkler Rough-in/Hydro4/26/20174/27/20174/27/2017APART
DetailsJim Page
Hydrostatic complete for overhead fire sprinkler piping. Rough to cover inspection complete for levels 1 and 2 of pod 4, rough in inspection complete for level 3, tenting to be installed at a later date.
INSP-Sprinkler Rough-in/Hydro4/26/20174/26/20174/26/2017PCANC
DetailsJim Page
Inspection request rescheduled per conversation with Mike Phone #: ###-####
INSP-Sprinkler Rough-in4/11/20174/11/20174/11/2017PPART
DetailsJim Page
Rough to cover inspection for levels 1 and 2 of pod 3 complete, approved for cover. Rough in inspection complete for level 3, tenting needs to be installed/inspected and passed before cover can be approved.
INSP-Sprinkler Rough-in/Hydro4/3/20174/4/20174/4/2017APART
DetailsJim Page
Tenting inspection for south east apartment unit of pod 2, level 3 complete, approved for cover.
INSP-Sprinkler Rough-in3/31/20174/3/20174/3/2017APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler pipe tenting partially complete, approved for cover except the south east apartment unit of pod 2, level 3, no insualtion installed
INSP-Conference3/7/20173/7/20173/7/2017ADONE
DetailsJim Page
Fire conference complete for soffit addition in residant rooms for fresh air vent, heads will spray under soffit with adjusted spacing of room heads.
INSP-Sprinkler Rough-in/Hydro2/27/20172/28/20172/28/2017APART
DetailsJim Page
Tenting inspection for pod 1, level 3 complete, approved for cover.
INSP-Sprinkler Rough-in2/24/20172/27/20172/27/2017ACANC
DetailsJim Page
3RD FLOOR tenting inspection request is rescheduled for 28FEB2017 per conversation with general contractor.
INSP-Sprinkler Rough-in2/23/20172/24/20172/24/2017APART
DetailsJim Page
Rough to cover inspection for Pod 2 complete, levels 1 and 2 approved for cover, level 3 cannot be completed until tenting inspection is complete.
INSP-Supply line flush2/14/20172/16/20172/16/2017ADONE
DetailsJim Page
Underground main line flush complete
INSP-Sprinkler Rough-in/Hydro2/13/20172/14/20172/14/2017APASS
DetailsJim Page
Underground hydrostatic test complete
INSP-Sprinkler Rough-in/Hydro2/10/20172/10/20172/10/2017PPART
DetailsJim Page
Partial rough to cover inspection complete for levels 1, mezzanine, and level 2, notated the city approved drawings with yellow highlighter red ink area's approved for cover. Rough in inspection is complete for level 3 in highlighted area on city approved drawings. Level 3 piping cannot be covered until tenting inspection is complete and passed.