Permit Information
Permit NumberFIR16-00565
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5820 W HILL RD
Project NameMichaud Residence
Customer Number 
ePlanReviewYes
Description
[Michaud Residence]
The fire sprinkler scope of work consists of protecting a three level dwelling. The system is supplied by a tank and a pump rated at 50 Gpm @ 40 Psi. The system uses residential sprinklers and CPVC piping.

[BLD16-01003] - WUI Zone A; Permit for the construction of a new 3399 sq. ft., two story (first story 816 sq. ft., second story 1296 sq. ft., third story 1287 sq. ft.) single family dwelling with 4 bedrooms, 3.5 bathrooms, approximately 320 sq. ft. of balcony, 70 sq. ft. covered porch, 210 sq. ft. sunroom, 210 sq. ft. covered car port and a 545 sq. ft. attached garage per the approved plans, engineering, ACCA report and any notations. R-1C zoning and setbacks per planning. //leg
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/8/201612/9/201612/9/2016APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Final Inspection12/2/201612/5/201612/5/2016ACANC
DetailsJim Page
Inspection request is rescheduled per conversation with foreman.
INSP-Final Inspection11/18/201611/23/201611/23/2016PPART
DetailsJim Page
Partial final for fire sprinkler system complete, walk-through for house complete. Fire sprinkler system is supplied by stand-alone tank and pump, electricians have not supplied power to the pump, inspection request will be scheduled when pump is powered and ready to flow water.
INSP-Final Inspection11/17/201611/21/201611/18/2016PCANC
DetailsJim Page
Jim Baker is the contact for this inspection. He needs a final inspection. Please give Jim a hour notice as he will be working in Caldwell at another site. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in9/29/20169/29/20169/29/2016PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, previously noted noted have been addressed/repaired. Fireplace framing does not go all the way to the ceiling, discussed this with Tim Frost due to tthe approved drawings showing a head in the gas fireplace enclosure, due to this application Tim is okay with the head not being in place, fire sprinkler coverage around fire place is adequete. Overhead fire sprinkler piping and tenting of overhead fire sprinkler piping approved for cover.
INSP-Sprinkler Rough-in9/21/20169/22/20169/22/2016AFAIL
DetailsTroy Cobbley
See the city approved plans for corrections marked in red which include incorrect tenting, lack of coverage in the toilet area, missing nailer plates, cpvc pipe to far from wall at pump/riser, lack of heat in Sun Room for the two pendants. Also piping has been covered in the Sun Room (needs tenting or dry heads) and in the Garage. Also Tim provided note about staying minimum 3' from fixtures which has not been adhered to. Piping can not be covered.