INSP-Final Inspection | 12/8/2016 | 12/9/2016 | 12/9/2016 | A | PASS |
Jim Page
|
|
|
Final fire sprinkler inspection passed/complete
|
INSP-Final Inspection | 12/2/2016 | 12/5/2016 | 12/5/2016 | A | CANC |
Jim Page
|
|
|
Inspection request is rescheduled per conversation with foreman.
|
INSP-Final Inspection | 11/18/2016 | 11/23/2016 | 11/23/2016 | P | PART |
Jim Page
|
|
|
Partial final for fire sprinkler system complete, walk-through for house complete. Fire sprinkler system is supplied by stand-alone tank and pump, electricians have not supplied power to the pump, inspection request will be scheduled when pump is powered and ready to flow water.
|
INSP-Final Inspection | 11/17/2016 | 11/21/2016 | 11/18/2016 | P | CANC |
Jim Page
|
|
|
Jim Baker is the contact for this inspection. He needs a final inspection. Please give Jim a hour notice as he will be working in Caldwell at another site. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 9/29/2016 | 9/29/2016 | 9/29/2016 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, previously noted noted have been addressed/repaired. Fireplace framing does not go all the way to the ceiling, discussed this with Tim Frost due to tthe approved drawings showing a head in the gas fireplace enclosure, due to this application Tim is okay with the head not being in place, fire sprinkler coverage around fire place is adequete. Overhead fire sprinkler piping and tenting of overhead fire sprinkler piping approved for cover.
|
INSP-Sprinkler Rough-in | 9/21/2016 | 9/22/2016 | 9/22/2016 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for corrections marked in red which include incorrect tenting, lack of coverage in the toilet area, missing nailer plates, cpvc pipe to far from wall at pump/riser, lack of heat in Sun Room for the two pendants. Also piping has been covered in the Sun Room (needs tenting or dry heads) and in the Garage. Also Tim provided note about staying minimum 3' from fixtures which has not been adhered to. Piping can not be covered.
|