Permit Information
Permit NumberFIR16-00577
StatusIssued
Name PROTEX
Site Address 12435 W USTICK RD
Project NameUstick Portable
Customer Number 
ePlanReviewYes
Description
Install a new code-compliant fire alarm system in a modular building.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/21/20169/22/20169/22/2016APART
DetailsTroy Cobbley
A temporary for the fire alarm is ok per the fire dept until the knox key box has been installed.
INSP-Final Inspection9/16/20169/19/20169/19/2016PFAIL
DetailsTroy Cobbley
Provide as-builts showing the correct communicator (DSC), provide breaker lock and breaker description on the schedule with-in the breaker panel, provide knox key box per review note #13 (Building is a separate fire alarm system from main school).