Permit Information
Permit NumberFIR16-00608
StatusFinaled
Name PEAK ALARM
Site Address 2710 W SUNRISE RIM RD Unit: 100
Project NameMFHI Sunset Rim
Customer Number 
ePlanReviewYes
Description
Remove a couple of walls and remount existing strobes in unit, no addition of equipment or wire. No change to existing system. This work is associated with building permit BLD16-02809.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/12/20181/12/20181/12/2018PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in8/31/20178/31/20178/31/2017PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection11/3/201611/4/201611/4/2016PFAIL
DetailsTroy Cobbley
No testing performed. Two strobes are placed too low and one of these two is overspaced from a side wall. Also the provided city approved fire alarm plans have been printed off too small to be legible. Provide larger plans
INSP-Conference11/1/201611/1/201611/1/2016PDONE
DetailsTroy Cobbley
I spoke to Mike about getting this inspection scheduled and finaled. He is going to follow up and hopefully schedule for this week.
INSP-Final Inspection9/27/20169/27/20169/27/2016PCANC
DetailsJim Page
Superintendent of project, Steve Phone #: ###-#### scheduled the inspection request, alarm contractor was not notified, alarm vendor needs to be onsite for fire alarm system inspection. This inspection request cancelled and alarm vendor will need to schedule final fire alarm inspection request.