INSP-Final Inspection | 3/10/2017 | 3/10/2017 | 3/10/2017 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
INSP-Final Inspection | 3/6/2017 | 3/7/2017 | 3/7/2017 | A | PART |
Troy Cobbley
|
|
|
A temporary is being given with the fire dept approval until the as-builts have been approved.
|
INSP-Alarm Testing | 3/1/2017 | 3/2/2017 | 3/2/2017 | P | FAIL |
Troy Cobbley
|
|
|
No testing performed. Manual pull stations are mounted too high, strobe in cooler is overspaced, smoke detectors are mounted too low, no map, no knox box, no as-builts
|