Permit Information
Permit NumberFIR16-00648
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 213 N 9TH ST
Project Name1st FLOOR LOBBY CEILING REMOEL
Customer Number 
ePlanReviewYes
Description
[9th & Idaho Building Lobby Remodel] - Quick Permit
NO NEW WALLS JUST REMODELING THE CEILING IN THE 1st FLOOR LOBBY.
REPLACING THE EXISTING QR HEADS WITH NEW CONCEALED QR HEADS AS SHOWN AND RELOCATING HEADS TO NEW CEILING LAYOUT.

[BLD16-01324] - This building is fire sprinklered to comply with high-rise provisions. Permit is to remodel an existing 1,615 sq. ft. lobby area within an existing 8 story building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select non-load bearing brick, removal of select furred out walls, removal of select gypsum ceiling, removal of select suspended acoustic ceiling, construction of select non-load bearing walls, construction of select gypsum ceiling soffit, relocate existing light fixtures, electrical work, mechanical ductwork and interior finishes to be in compliance with Ch. 8 of the 2012 IBC. Note: existing one hour rated lobby corridor walls to be maintained. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/21/201612/22/201612/22/2016APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete.
INSP-Sprinkler Rough-in11/17/201611/17/201611/17/2016PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.