INSP-Final Inspection | 6/7/2017 | 6/8/2017 | 6/8/2017 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/31/2017 | 6/2/2017 | 6/2/2017 | P | FAIL |
Jim Page
|
|
|
Fire sprinkler head is to far off of wall, east space near fire sprinkler riser room wall. Heads are still masked from painters in east section of building by seperating wall. Signage needs to be installed on valves/riser trim in fire pump/fire riser room. PODS section office area shows walls going all the way to the deck as shown on fire sprinkler city approved drawings as well as BLD permit city approved drawings, walls do not go all of the way up, fire sprinklers will need to be added or walls will need to go all of the way up to roof deck Fire bell signage needs to be installed on exterior bell. Fire sprinkler riser room signage needs to be installed on exterior door for fire riser/fire pump room.
|
INSP-Sprinkler Rough-in/Hydro | 5/30/2017 | 5/31/2017 | 5/31/2017 | A | PASS |
Scott Arellano
|
|
|
Hydr test on 2 systems OK.
|
INSP-Sprinkler Rough-in/Hydro | 5/30/2017 | 5/31/2017 | 5/30/2017 | P | CANC |
Jim Page
|
|
|
Gabe Garduno is the contact for this inspection. He is requesting an overhead hydro in the PM if possible. Thank you for your help. Phone #: ###-#### >> Inspection requested via web by Kay Haney Inspection cancelled from web by: Kay Haney
|
INSP-Sprinkler Rough-in | 4/24/2017 | 4/26/2017 | 4/26/2017 | P | DONE |
Jim Page
|
|
|
Fire pump start-up complete.
|
INSP-Conference | 3/10/2017 | 3/10/2017 | 3/10/2017 | P | DONE |
Troy Cobbley
|
|
|
I left message for the fitter and stopped at the project site but made no contact except I did speak to the job superintendant. The answer to the question on whether each head under the furnaces had to be separate is "yes". Two or more heads can not be combined on a single drop. Each head needs its owner supply.
|
INSP-Sprinkler Rough-in | 2/28/2017 | 2/28/2017 | 2/28/2017 | P | PART |
Troy Cobbley
|
|
|
Rough-in for the most part passed. Items noted needing correction are branchline restraints are not installed as per plan and are therefore overspaced (54' max.), siesmic bracing of the main piping is missing in several locations and has been noted in "red" on plans and per phone conversation with Tom it appears that the bracing designated as SB-3 (1 1/4") needs to be used on all of the 4" mains (1" has been used), it also appears that sprinkler protection is required below all of the unit heaters (Tom is going to investigate), it appears that the ESFR heads are overspaced in two locations at the Fire Pump/Mechanical Room walls, there is a possible obstruction to the ESFR heads in the south east corner of the warehouse at a HVAC duct penatration.
|