INSP-Final Inspection | 11/16/2017 | 11/17/2017 | 11/17/2017 | A | PASS |
Troy Cobbley
|
|
|
Permit can be finaled. A separate permit has been issued for this same work as per Shane with SimplexGrinnell. That permit is FIR17-00673
Colton Phone #: ###-####
|
INSP-Final Inspection | 4/20/2017 | 4/21/2017 | 4/21/2017 | A | FAIL |
Troy Cobbley
|
|
|
The notification devices with-in the tenant space have been corrected and test. But the notification devices in the path of egress have not been corrected as per email requirement from the fire dept. Email forwarded to Nathan with Simplex
|
INSP-Final Inspection | 12/27/2016 | 12/28/2016 | 12/28/2016 | A | FAIL |
Troy Cobbley
|
|
|
The new strobes are mounted too low. Installer apparently matched existing heights. I need the new devices to be installed at the correct height and the existing strobes in the remodel area/path of egress to meet current code or provide verification that they met code when they were installed.
|
INSP-Final Inspection | 12/27/2016 | 12/27/2016 | 12/27/2016 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled for tomorrow morning.
|