Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR16-00738
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 S ALLUMBAUGH WAY
Project NameMorning Star Memory Care
Customer Number 
ePlanReviewYes
Description
[Morning Star Memory Care]
The fire sprinkler scope of work consists of a one level memory care facility with and attic, protected per NFPA 13. There are two 6” dry systems and one 4” wet system which are supplied by 6” underground through a 6” backflow preventer to a 6” header. The two dry systems are looped and utilize a combination of, standard QR sprinklers and attic sprinklers. The wet system is tripled looped

The underground piping is under permit FIR16-00645

[BLD16-02899] – Permit for the construction of a new 43,986 sq. ft. memory care building with 50 dwelling/sleeping units, a commercial kitchen, associated dining areas, a theater room, coffee bar and an activity room and two outdoor courtyards per the approved plans and the attached engineering. This building is to be fire sprinklered with a NFPA 13 system with an alarm and shall comply with NFPA 13 and 72 as required by the Boise City Building department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/5/20179/5/20179/5/2017PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/31/20179/1/20179/1/2017AFAIL
DetailsTroy Cobbley
The interconnection with the fire alarm panel needs to be retested due to wrong signals from tamper and pressure switches. Also need the forward flush test for 13psi out of the 2 1/2" drain. Need test papers as well

Adam Phone #: ###-####
INSP-Sprinkler Rough-in7/17/20177/18/20177/18/2017APASS
DetailsTroy Cobbley
The remaining sprinkler piping can be covered. The remaining tenting passed. There are a few can lights that are close to the new pendant sprinklers that I will need verification on.
INSP-Conference7/13/20177/14/20177/14/2017ADONE
DetailsTroy Cobbley
Kitchen area piping is ok to cover.
INSP-Conference6/15/20176/16/20176/16/2017APASS
DetailsTroy Cobbley
See the city approved plans for more locations marked ok where tenting is approved and piping can be covered.
INSP-Sprinkler Rough-in6/2/20176/2/20176/2/2017PPASS
DetailsTroy Cobbley
See the city approved plans for additional areas marked "ok" where tenting is passed and piping can be covered.
INSP-Sprinkler Rough-in5/31/20176/1/20176/1/2017PPASS
DetailsTroy Cobbley
See the city approved plans for additional areas/rooms where tenting is complete and piping can be covered.
INSP-Conference5/23/20175/24/20175/24/2017APASS
DetailsTroy Cobbley
See the city approved plans for additional rooms where the wet system tenting inspection is passed and the piping can be covered in the North end of the building tenant rooms only
INSP-Sprinkler Rough-in5/18/20175/18/20175/18/2017PPASS
DetailsTroy Cobbley
The two rooms that had been covered prior to a tenting inspection are now approved for cover
INSP-Sprinkler Rough-in/Hydro5/17/20175/18/20175/18/2017APASS
DetailsTroy Cobbley
24 hr air test for the dry system passed
INSP-Sprinkler Rough-in/Hydro5/16/20175/17/20175/17/2017APART
DetailsTroy Cobbley
Air test started at 7:30am with 43psi on both dry systems
INSP-Sprinkler Rough-in/Hydro5/16/20175/16/20175/16/2017PPASS
DetailsTroy Cobbley
Wet system hydro test passed. Also the sprinkler heads that have been added to the combustible concealed spaces above the fire places are ok to cover.
INSP-Conference5/10/20175/10/20175/10/2017PPASS
DetailsTroy Cobbley
See the city approved plans for areas marked OK where tenting has passed inspection and the piping can be covered. Herb and I also discussed making the fake beams out of non-combustible material so that sprinkler protection will not be required inside.
INSP-Sprinkler Rough-in/Hydro5/4/20175/5/20175/5/2017APASS
DetailsTroy Cobbley
The remaining rough-in for the wet system basically passed with some small items that need addressed. First the plans/calculations need to be re-approved showing the additional 90's and the combustible concealed spaces at the columns and fire places need addressed. Also four dry pendants have not been installed which also needs approved.
INSP-Sprinkler Rough-in/Hydro5/4/20175/5/20175/5/2017APASS
DetailsTroy Cobbley
200psi test of both dry systems passed
INSP-Sprinkler Rough-in/Hydro4/26/20174/27/20174/27/2017AFAIL
DetailsTroy Cobbley
24 hour air test failed.
INSP-Sprinkler Rough-in4/25/20174/26/20174/26/2017APART
DetailsJim Page
24 hour air test started at 0930, west dry pipe riser at 42 psi, east at 40 psi. Partail rough in inspection completed on wet and dry systems, notated city approved drawings with red ink area's that were inspected, tenting to be installed at a later date for wet system on area's inspected (Piping cannot be covered until tenting is complete and inspected). Notated city approved drawings 2 units where the tenting was complete, area's noted tenting completion are approved for cover.
INSP-Sprinkler Rough-in4/20/20174/20/20174/20/2017PPASS
DetailsTroy Cobbley
See the city approved plans for two rooms marked ok where piping can be covered at the south end of the project. Also the new canopy over the main entrance can be covered
INSP-Sprinkler Rough-in4/17/20174/17/20174/17/2017PPASS
DetailsTroy Cobbley
See the city approved plans for annotations with todays date where sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in4/10/20174/11/20174/11/2017APART
DetailsTroy Cobbley
Todays inspection was for the same area as previously inspected but for tenting. All tenting in this area is ok except one small spot. I discussed with Herb that prior to a cover inspection being given I need verification of insulation in the eaves to keep the sprinkler coverage with-in the 30' requirements and to verify insulation in the dog houses.
INSP-Sprinkler Rough-in/Hydro3/29/20173/30/20173/30/2017PPART
DetailsTroy Cobbley
See the city approved plans with notations in red for areas of the wet system and dry system inspected. I noted that I need access to the dog houses to verify insulation, sway bracing attachment needs to be verified. Tenting had been started but was not complete so all tenting will need to be verifed. Also the wet system remote area needs re-verified due to pipe routing changes near the closet area on the most remote line in the hydraulic calc. area.