Permit Information
Permit NumberFIR16-00760
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7470 W SAXTON DR
Project NameKensington Apartments Bldg G
Customer Number 
ePlanReviewYes
Description
[Kensington Apartments - Building G]
The fire sprinkler scope of work consists of a NFPA 13R system for a four level apartment building. The system is supplied by 2” underground through a 2” backflow preventer to (4) 2” risers. There are floor level control valves in a valve house. The system piping is CPVC with extended coverage residential sprinklers.

There is a 4” standpipe with (4) 6” risers. Each standpipe riser has (3) hose valves. The FDC is connected to the standpipe per the fire marshal’s office. Each riser has a supervised sectional control valve.

[BLD15-01124] - The drawings are filed under BLD15-01118 in ePlanReview. The NFPA 13-R fire sprinkler system is used for occupancy and for story increase. To construct a 39,150 square foot four story apartment building (10,031 sq. ft. 1st story with four 3.b units and four 1.c units, 10,031 sq. ft. 2nd story with four 3.b units and four 1.c units, 10,031 sq. ft. 3rd story with four 3.b units and four 1.c units, 9,057 sq. ft. 4th story with four 2.d units and four 1.c units). All ground floor units are required to comply as Type B dwelling units. No elevator is provided in this building. Work is to include concrete footings, concrete foundations, concrete slabs on grade, wood stud bearing walls, wood stud shear walls, fiberglass shingles, fiber-cement board siding, manufactured stone veneer, 1-hr dwelling unit separations, .5-hr minimum fire-resistance-rated corridors with 20-minute smoke- and draft-control doors, exterior exit stairways fire rated like the corridor, steel stairways with concrete treads, interior nonbearing walls, millwork, and finishes. Special Inspection is required for soils and for concrete. The roof truss design is a deferred submittal item. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13-R and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/1/20178/2/20178/2/2017APASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Supply line flush6/14/20176/15/20176/15/2017APASS
DetailsTroy Cobbley
underground flush passed
INSP-Sprinkler Rough-in/Hydro5/2/20175/3/20175/3/2017APASS
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping located on level 4 complete, rough to cover inspection for overhead fire sprinkler piping/tenting on fre fire sprinkler piping located in attic spaces compete, approved for cover.
INSP-Sprinkler Rough-in/Hydro5/2/20175/2/20175/2/2017PCANC
DetailsJim Page
Inspection request rescheduled for 3MAY2017
INSP-Sprinkler Rough-in/Hydro4/24/20174/25/20174/25/2017APART
DetailsJim Page
Hydrostatic test complete for levels 2 and 3, rough to cover inspection complete for level 2, level 2 approved for cover, partial cover approved for level 3, overhead fire sprinkler piping in attic space cannot be covered until tenting is installed and passed inspection.
INSP-Sprinkler Rough-in/Hydro4/24/20174/24/20174/24/2017PCANC
DetailsJim Page
Inspection request cancelled per conversation with Jake ###-#### Inspection requested will be rescheduled by contractor.
INSP-Sprinkler Rough-in/Hydro4/19/20174/21/20174/21/2017PPART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping on level 1 complete, approved for cover on level 1 only. Hydrostatic test complete for overhead fire sprinkler piping on level 1, levels 2, 3 and 4 to have hydrostatic test completed at a later date.
INSP-Sprinkler Rough-in/Hydro3/22/20173/22/20173/22/2017PPASS
DetailsJim Page
Underground hydrostatic test complete
INSP-Supply line flush3/21/20173/22/20173/22/2017PCANC
DetailsJim Page
Incorrect inspection request, request is for an underground hydro, this request cancelled and the correct request generated.
INSP-Sprinkler Rough-in/Hydro3/20/20173/23/20173/21/2017PCANC
DetailsJim Page
Underground rough/hydro - call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Supply line flush3/20/20173/21/20173/20/2017PCANC
DetailsJim Page
Underground rough/hydro - call Jake when heading out. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in3/17/20173/17/20173/17/2017PPASS
DetailsJim Page
Rough to cover inspection for underground supply complete, approved for cover.
INSP-Supply line flush3/17/20173/17/20173/17/2017PCANC
DetailsJim Page
INSP-Supply line flush3/15/20173/16/20173/16/2017ACANC
DetailsJim Page
Inspection request cancelled per conversation with point of contact Jake Phone #: ###-#### due to complications, request will be reschedule.
INSP-Sprinkler Rough-in/Hydro2/9/20172/9/20172/9/2017PPASS
DetailsJim Page
Rough in/hydro for standpipe complete
INSP-Sprinkler Rough-in/Hydro2/8/20172/8/20172/8/2017PCANC
DetailsJim Page
Standpipe rough/hydro inspection cancelled per conversation with point of contact, Jake Phone #: ###-####, inspection request will be scheduled for a later date.