Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberFIR16-00819
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 8000 S FEDERAL WAY
Project NameMicron Bldg 39 TCUP - Udg Only
Customer NumberUDG ONLY
ePlanReviewYes
Description
Installation of 6"x37' ± C-900 piping and 6"X11' of DI piping. With a PIV, thrust blocks and fitting.

There does not seem to be an associated building permit at this time.

(No written review)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/16/20197/17/20197/17/2019APASS
DetailsJim Page
Final inspection for underground supply complete.

Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Sprinkler Rough-in/Hydro7/16/20197/17/20197/17/2019ADONE
DetailsJim Page
Hydrostatic test for underground supply has been witnessed and completed.

Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
INSP-Supply line flush11/20/201711/21/201711/21/2017PDONE
DetailsJim Page
Underground supply flush complete.
INSP-Supply line flush11/20/201711/20/201711/20/2017PCANC
DetailsJim Page
Inspection request is for 21NOV2017, this request is cancelled.
INSP-Sprinkler Rough-in1/12/20171/13/20171/13/2017PPART
DetailsJim Page
Partial rough to cover inspection for underground supply complete, remaining underground which includes PIV will be installed at a later date. Piping installed consist of stub up and ductile iron for under footing, installed underground piping is approved for cover.
INSP-Sprinkler Rough-in1/12/20171/12/20171/12/2017PCANC
DetailsJim Page
Inspection request per conversation with point of contact, Chris Phone #: ###-####, inspection request will be rescheduled for a later date.