Permit Information
Permit NumberFIR17-00061
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1387 S VINNELL WAY
Project NameGSA BLM 3RD FLOOR TI - PH I&II
Customer Number 
ePlanReviewYes
Description
GSA BLM TI job is to add notification devices to the area of work. Existing NAC panel and ckts in area of work, we are going to split exiting NAC ckt, adding new and relocating existing devices. THis work is associated with building permit BLD16-04264.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/17/20174/20/20174/20/2017APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/23/20172/24/20172/24/2017APART
DetailsTroy Cobbley
A temporary is being given with Assistant Chief Ron's permission until the audible sync issue has been addressed through a permit or an upgrade agreement.
INSP-Final Inspection2/21/20172/22/20172/22/2017AFAIL
DetailsTroy Cobbley
We did not actually test today due to conversation with Building Manager (steve), and the installing contractor (scott) for the fire alarm system modifications. They changed out two devices but there are more that are creating an issue. I deferred Steve to Ron with the Boise Fire Dept. for a possible upgrade agreement.
INSP-Final Inspection2/17/20172/21/20172/21/2017AFAIL
DetailsTroy Cobbley
The audible alarm shall be temporal. When tested the new devices are temporal but atleast one of the existing devices is a solid tone. I went over code requirements for audilble and visual devices.