Permit NumberFIR17-00080
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1747 N FAIRMEADOW DR
Project NameTHE VILLAGE CHARTER SCHOOL
Customer Number 
ePlanReviewYes
Description
[Village Charter School]
The fire sprinkler scope of work consists of protecting a new school which is being converted from an existing strip. There are two building. This is building one. There will be two new 4” dry pipe systems with above and below protection. Some of the above protection will be combustible concealed spaced sprinklers.

Plan Mod #1 – 4/11/2017
Revised the protection in the attic. Removed some CC2 sprinklers and added some CC2 sprinklers elsewhere.

[BLD16-00124] – This project also being done in conjunction with BLD16-00161 on same set of plans. Remodel of an existing 24,500 sq. ft. office/retail building into new educational charter school with new classrooms and school administration offices per approved plans. New parking lot design and outdoor area for the kids. Work to include seismic upgrade from Risk Category II to Risk Category III, new interior walls, interior finish, fire sprinkler work, fire alarm work, plumbing work, mechanical work, and electrical work. Special Inspections required for structural steel, concrete and soils. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **ajs**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/14/20177/17/20177/17/2017PPASS
DetailsJim Page
Final fire sprinkler inspection for this area of work passed/complete.
INSP-Final Inspection7/13/20177/14/20177/14/2017AFAIL
DetailsTroy Cobbley
The fire alarm system was not ready to verify the tamper/flow/pressure switches, need system zone map, signage on door, and plan modifications showing the dry pipe valves used. Also missing the spare sprinkler cabinet. The forward flush test passed.
INSP-Sprinkler Rough-in/Hydro7/7/20177/7/20177/7/2017PPASS
DetailsTroy Cobbley
24 hour air test for system 1 and 2 passed
INSP-Sprinkler Rough-in7/5/20177/6/20177/6/2017APART
DetailsTroy Cobbley
24 Hour Air test started at 8:00am with 46psi on the left system and 45 1/2psi on the right system.
INSP-Sprinkler Rough-in/Hydro6/30/20177/5/20177/5/2017APASS
DetailsTroy Cobbley
System #1 and #2 overhead hydro tests passed
INSP-Supply line flush6/20/20176/21/20176/21/2017PDONE
DetailsJim Page
Underground main line flush complete
INSP-Sprinkler Rough-in6/6/20176/7/20176/7/2017APASS
DetailsTroy Cobbley
The exterior canopy at the south building, east end is complete and sprinkler rough-in passed. Piping can be covered.
INSP-Sprinkler Rough-in/Hydro5/30/20175/31/20175/31/2017APASS
DetailsTroy Cobbley
The underground and system #2 hydro tests passed
INSP-Sprinkler Rough-in5/12/20175/12/20175/12/2017PPASS
DetailsTroy Cobbley
Underground cover passed. Piping has been mechanicaly restrained. Brian is going to also add concrete thrust blocks. Piping can be covered.
INSP-Sprinkler Rough-in5/9/20175/9/20175/9/2017PPASS
DetailsTroy Cobbley
The remaining tenting is complete for the north half of the building and the piping can be covered. The new canopy at the south end of the building still needs inspected when built.
INSP-Sprinkler Rough-in5/5/20175/8/20175/8/2017APASS
DetailsTroy Cobbley
The remaining piping rough-in passed. Piping can not be covered until a tenting inspection has been scheduled
INSP-Sprinkler Rough-in4/27/20174/28/20174/28/2017APASS
DetailsTroy Cobbley
Rough-in inspection passed for piping from the south end to the CMU wall as marked on the plans. Piping can be covered except around the sky lights. Mark is going to follow up on the need for sidewalls in the two sky lights.
INSP-Sprinkler Rough-in4/25/20174/26/20174/26/2017AFAIL
DetailsTroy Cobbley
Todays inspection was for another area for cover. I stopped inspection when I found missing uprights in canopy and different heads installed in building. Plans need to be provided/submitted that show the actual heads installed. I gave the ok to cover in the previous area where upright have been removed and batt insulation provided.
INSP-Sprinkler Rough-in4/13/20174/14/20174/14/2017APASS
DetailsTroy Cobbley
See the city approved plans for location where piping can be covered as marked with todays date. Still need to view piping when the south canopy is built and need to view insulation in the combustible space as discussed.
INSP-Sprinkler Rough-in4/11/20174/11/20174/11/2017PPART
DetailsTroy Cobbley
Resubmitted plans have been approved for the area inspected yesterday but insulation has been installed that blocks the CC2 heads on two branchlines.
INSP-Sprinkler Rough-in4/11/20174/11/20174/11/2017PPART
DetailsTroy Cobbley
This inspection was actually performed on 4/10/17 but was input under the wrong permit number.

Rough to cover inspection passed for area marked on the city approved plans. I noted one missing sprig up that was being installed as I waited. East canopy has not been built or piping installed yet. Plans need to be resubmitted for approval showing the changing of the standard heads to the CC2's prior to more cover inspections being approved.