Permit NumberFIR17-00198
StatusFinaled
Name STATEFIRE DC SPECIALTIES
Site Address 3625 W ELDER ST
Project NameComfort Inn Suites
Customer NumberUDG ONLY
ePlanReviewYes
Description
[Comfort Ins Suites - Undeground Only] - Quick Permit
New 6"x 320'± C-900 Underground with necessary fittings and thrust blocks.

[BLD17-00022] - (COMFORT SUITES) For the construction of a new 108 room 4 story wood framed hotel with work to include general site work and utilities. The first story is 15,970 sq. ft. consists of 12 sleeping rooms, a pool, general off, laundry room, lobby and a breakfast area and the 900 sq. ft. porte cochere, the remaining 3 stories are 15,114 sq. ft. each with 32 sleeping units on the 2nd and 3rd stories and 33 units on the 4th story. This building is fully fire sprinklered with an NFPA 13 system for area increase
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/28/20186/28/20186/28/2018PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro6/7/20186/11/20186/11/2018PPART
DetailsTroy Cobbley
24hr test started at 9:00an with 40psi on the guage. First and second floor hydro tests passed.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
INSP-Sprinkler Rough-in/Hydro6/7/20186/8/20186/8/2018APASS
DetailsTroy Cobbley
2nd,3rd floor hydro tests passed.
INSP-Supply line flush11/8/201711/8/201711/8/2017PPASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Supply line flush8/7/20178/8/20178/8/2017APASS
DetailsTroy Cobbley
The underground flush passed
INSP-Sprinkler Rough-in/Hydro8/7/20178/7/20178/7/2017PPASS
DetailsTroy Cobbley
Underground hydro test passed
INSP-Sprinkler Rough-in5/4/20175/8/20175/8/2017APASS
DetailsTroy Cobbley
Bury depth has been verifed with laser and is ok to cover.
INSP-Sprinkler Rough-in5/5/20175/5/20175/5/2017PPASS
DetailsTroy Cobbley
Underground supply piping is ok to cover. A letter is being provide by the underground installer stating that the min. 4'6" cover has been provided for all of the piping